EDS - TECHNICAL INSTRUCTIONS
3
QUICK INSTALLATION
The procedure below is intended for trained personell with previous experience in installing EDS Beam Smoke Detectors
RK100-B and RK100-BS. If you don’t have the needed experience please refer to the standard installation procedure of
this manual. On our site
www.eds.eu
is available a video with instructions for installing the RK detectors.
1 - Mount the RK100-B detector (TX + RX)
2 - Connect the cables
3 - Make the optical allignment with the Laser Pointer BLP-100 with the procedure set out in cap. 7
4 - Set SW3 switch on the TX according to the distance TX/RX (see table in fig.7) and power up the TX
5 - Set the JP2-JP3-JP4-JP5-JP7 jumpers on the RX (see pag.13)
6 - Place RX jumper JP1 in “ON” position (Alignment) power up the RX device.
7 - Optimize the device signal using:
•
the adjustment screws V1-V2-V3 on the optical block on the TX
•
the P1 trimmer on the RX
•
a multimeter (or the STS01 instrument)
•
Blue/Red Led signal level indication (fig.8 board)
8 - Regulate the signal between 4,7V and 5V with the P1 trimmer
9 - Select the desired sensibility of the Obscuration circuit with the SW2 selector (40-50-60-70%)
10 - Select the desired sensibility of the Turbulence (Heat) circuit with the SW1 selector (if used - not present
in -S version)
11- Check the detector’s operation by obscuring the TX or the RX
12 - Set JP1 in the OFF position to activate the device
13 - Close the cover within 5 minutes
14 - Wait at least 5 minutes for the device to become operational
15 - Perform operational tests