EDS - TECHNICAL INSTRUCTIONS
19
P1 -
trimmer for the regulation of the signal level. Normally regulated to 50-60% that corresponds to a signal of 5V at the
maximum distance
SW1
- selector for the regulation of the sensitivity of the Turbulence circuit. Sensitivity increases from 1 to 4. Position 1,
minimum, position 4, maximum.
Not present in -S version.
SW2 -
trimmer for the regulation of the sensitivity of the circuit sensible to Obscuration
• low sensitivity - alarm level for obscuration at 70%, position 1
• middle / low sensitivity - alarm level for obscuration at 60%, position 2
• middle / high sensitivity - alarm level for obscuration at 50%, position 3
• high sensitivity - alarm level for obscuration at 40%, position 4
V1-V2-V3
- scews for the regulation of the optical block
CN4
- connector for the STS-01 meter (optional)
JP1
- jumper for activate / deactivate the procedure of optical alignment.
To activate the procedure of optical alignment JP1 jumper must be inserted (ON).
To deactivate the procedure of optical alignment and therefore get the detector operational, the JP1 jumper must be
disconnected (OFF)
• JP1 position 2-3 (ON)......alignment procedure activated
• P1 position 1-2 (OFF)...... alignment procedure deactivated
JP2 - JP3 - JP4
- jumpers to set the relay contacts, respectively of the alarm relay, turbulence and fault normally closed
NC or normally open NO.
• position 1-2 - output contact normally open NO
• position 2-3 - output contact normally closed NC
JP4 must be in position 1-2 to have the contact closed because the fault relay is normally activated.
The RK100-B(S) detector is normally factory preset with closed NC contacts.
For the alarm relay the indication of JP2 is valid if JP7 is in OFF position
JP5 -
jumper to activate the alarm memory function or to deactivate such function (to get the auto Reset of the detector)
• position 1-2 memory deactivated. When it stops the state of alarm the detector him autoripristina (Auto Reset)
• position 2-3 memory activated . In case of alarm the shores-bearer remains in alarm until tension is not removed for 5
second
JP6 -
jumper of microprocessor Reset
JP7 -
jumper to set alarm relay operation normally powered or not powered
• JP7 ON - alarm relay normally activated (in case of alarm deactivated). In this case the indication of the jumper JP2
inverted
• JP7 OFF - alarm relay deactivated (in case of alarm activates). In this case the indication of the jumper JP2 is according
JP8
- Total obscuration Fault option- JP8 ON = activated