23
• Connect gas service from meter to control assembly(s)
in accordance with ANSI Z223.1 and local codes or
utility. On multiple base boilers, connect gas service
with branch lines from common main. Individual branch
lines must be same size as inlet to gas valve. Ground
joint union should be installed in each branch line for
easy servicing of gas controls. Drip leg or trap should be
installed at bottom of vertical section of piping at inlet to
each branch line. Figure 36. Pipe compound resistant
to action of liquefi ed petroleum gases must be used on
all threaded pipe connections.
• Main gas supply line should be adequate to prevent
undue pressure drop. See Chart 5 for pipe sizes for
gas mains.
• Boiler and its gas connection must be leak tested
before placing boiler in operation.
• Boiler and its individual shutoff vlave must be
disconnected from gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2psi (3.5kPa).
• Boiler must be isolated from gas supply piping
system by closing its individual manual shutoff
valve during any pressure testing of gas supply
piping system at test pressures equal to or less
than 1/2 psig (3.5 kPa)
Chart 4
Minimum Gas Supply Pressure
Models
5.0 inches w.c.
300
500
600
1000
1300
1500
2000
2100
2500
2600
3000
Models
5.3 inches w.c.
400
700
800
900
1100
1200
1400
1600
1700
1800
1900
2200
2300
2400
2700
2800
2900
All
Models
Maximum Gas Supply Pressure
13.5 inches w.c.
All
Models
Manifold Pressure
3.5 inches w.c.
Chart 5
TABLE OF PIPE SIZES IN INCHES FOR GAS MAINS
(NATURAL GAS)
Boiler
No
20’ 30’ 40’ 50’ 60’ 80’ 100’ 125’ 150’
300
1¼
1¼
1¼ 1¼ 1¼ 1¼
1½
1½
1½
400
1¼
1¼
1¼ 1¼ 1½ 1½
1½
1½
2
500
1¼
1¼
1¼ 1½ 1½ 1½
2
2
2
600
1¼
1½
1½ 1½
2
2
2
2
2
700
1¼
1½
1½
2
2
2
2
2
2½
800
1½
1½
2
2
2
2
2
2½
2½
900
1½
2
2
2
2
2
2½
2½
2½
1000
1½
2
2
2
2
2½
2½
2½
2½
1100
2
2
2
2
2
2½
2½
2½
2½
1200
2
2
2
2
2½ 2½
2½
2½
3
1300
2
2
2
2½ 2½ 2½
2½
3
3
1400
2
2
2
2½ 2½ 2½
3
3
3
1500
2
2
2½ 2½ 2½ 2½
3
3
3
1600
2
2
2½ 2½ 2½ 2½
3
3
3
1700
2
2½
2½ 2½ 2½
3
3
3
3
1800
2
2½
2½ 2½ 2½
3
3
3
3
1900
2
2½
2½ 2½
3
3
3
3
3
2000
2
2½
2½ 2½
3
3
3
3
3
2100
2½
2½
2½
3
3
3
3
3
4
2200
2½
2½
2½
3
3
3
3
4
4
2300
2½
2½
3
3
3
3
3
4
4
2400
2½
2½
3
3
3
3
3
4
4
2500
2½
3
3
3
3
3
4
4
4
2600
3
3
3
3
3
4
4
4
4
2700
3
3
3
3
4
4
4
4
4
2800
3
3
3
4
4
4
4
4
4
2900
3
3
4
4
4
4
4
4
4
3000
3
4
4
4
4
4
4
4
4
CONNECTING GAS SERVICE
Figure 36