COMMISSIONING
Power the detector : LINE (2) LED lights.
●
After 1.5 ... 2 minutes the detector is enabled for operation.
●
Set SENSITIVITY (1) potentiometer on 0.
●
Simulate the presence of gas : release gas from an ordinary
●
cigarette lighter near the monitoring sensor.
When the gas concentration reaches the pre-alarm threshold
●
the ALARM (4) LED blinks.
When it reaches the alarm threshold, after a delay of about 20
●
seconds :
– the ALARM (4) LED lights and remains lit
– the internal buzzer sounds (only if terminals M - F1 are
without link).
– the operational relay closes the shut-off valve or switches on
an aeration fan.
Stop releasing gas : when the gas concentration near the
●
sensor falls below the threshold level :
– if the detector is Without latching alarm, the alarm ceases
and the ALARM (4) LED continues to blink slowly until the
RESET (5) button is pressed.
– if With latching alarm, the alarm status continues until the
RESET (5) button is pressed for at least five seconds.
If the detector controls a valve with manual reset this must be
●
re-opened.