ECP GLD361 Quick Start Manual Download Page 2

Ref: ds_GLD_0209 Ver1.0.   

Gas Leak Detection GLD

Page 2 of 4

E.C. Products Limited - Head Office

EC House, Amberley Way, Hounslow 

Middlesex, TW4 6BH, United Kingdom

Tel: 

+44 (0)20 8569 4100  

Fax: 

+44 (0)20 8569 4111

 

ECP reserves the right to change the information contained in this datasheet as and when required without notice. Users must take care to use the information contained in this leaflet. ECP will not 

accept the liability  for damages, loss and expenses that may be caused by omissions and errors in the information provided.

Wiring

Separate base and cover

1. 

Mount base on DIN rail and check that the securing elements 

2. 

hold it firmly in place.

Carry out the wiring according to the diagram and in 

3. 

observance of the regulations in force, using cables of: 

– 1.5 mm2 for power and relay control outputs 

– 1 mm2 for sensor with maximum distance of 50 meters or 

    1.5 mm2 with maximum distance of 75 meters.

Carry out “Link functions” to adapt detector to type of 

4. 

operational control.
Switch on power (230 V ~) and check the voltage across 

5. 

terminals L and N
Switch off power, replace cover on base and secure it with the 

6. 

two screws supplied.
You are advised not to insert more than two cables in a single 

7. 

terminal of the detector and if necessary to use external 

junction boxes.

GLD361

B– Gas sensor

Y1– N.O. solenoid valve with manual reset

Y2– N.C. solenoid valve

Y3– N.C. solenoid valve with manual reset

M– Aeration fan

Link functions:
M - F1  without link

  = internal buzzer enabled

 

with link 

 

= internal buzzer disabled

F2 - F3  without link

  = relay normally energised; in presence of 

 

 

    gas de-energised

 

with link

 

= relay normally de-energised; in presence 

 

 

    of gas energised

F3 - F4  without link

  = relay with latching alarm

 

with link 

 

= relay with non-latching alarm

Warning:

 Before changing link positions switch off power supply

GLD65x

B – Gas sensor

Y1 – N.O. solenoid valve with reset 230 V ~

Y2 – N.O. solenoid valve with reset 12 V –

M – Aeration fan

h1 – Blinking 230 V~

h2 – Siren 230 V~

h3 – Blinking 12 V~

h4 – Siren 12 V~

Link functions:
M- F1  without link

  = Internal buzzer and external alarm activated

 

with link

 

= internal buzzer and external alarm 

 

 

    disactivated

F2 - F3  without link

  = relay normally energised; in presence of 

 

 

    gas de-energised

 

with link

 

= relay normally de-energised; in presence 

 

 

    of gas energised

F3 - F4  without link

  = relay with latching alarm

 

with link

 

= relay with non-latching alarm

B2 - H2 with link

 

= B2 sensor not connected

B3 - H3 with link

 

= B3 sensor not connected

NB:

 For N.C. valves do not make link F2-F3

Warning:

 Before changing link positions switch off power supply

Summary of Contents for GLD361

Page 1: ...pm Alarm Thresholds Natural Gas 0 5 to 1 25 5000 to 12500ppm LPG 0 22 to 0 56 2200 to 5600ppm CO 0 02 to 0 05 200 to 500ppm Sensors Natural Gas GLD150 LPG GLD250 CO GLD350 Materials Base Nylon Cover ABS Ambient Storage 25 C to 60 C Operating 0 C to 45 C Order Codes GLD361 DIN rail Single Channel Gas Leak Detection Controller GLD651 DIN rail Single Channel Gas Leak Detection Controller GLD652 DIN r...

Page 2: ...more than two cables in a single 7 terminal of the detector and if necessary to use external junction boxes GLD361 B Gas sensor Y1 N O solenoid valve with manual reset Y2 N C solenoid valve Y3 N C solenoid valve with manual reset M Aeration fan Link functions M F1 without link internal buzzer enabled with link internal buzzer disabled F2 F3 without link relay normally energised in presence of gas ...

Page 3: ... This permits in the event of an alarm taking action under conditions of maximum safety Using the SENSITIVITY 1 potentiometer the thresholds can be adjusted within the limits established by the manufacturing standards Potentiometer towards increase in sensitivity Potentiometer towards decrease in sensitivity Alarm The alarm status brings about the action of the operational relay if normally de ene...

Page 4: ...he gas concentration reaches the pre alarm threshold the ALARM 4 LED blinks When it reaches the alarm threshold after a delay of about 20 seconds the ALARM 4 LED lights and remains lit the internal buzzer sounds only if terminals M F1 are without link the operational relay closes the shut off valve or switches on an aeration fan Stop releasing gas when the gas concentration near the sensor falls b...