49
ECOScience ENERGY CENTRE
INSTALLATION AND USER MANUAL
© ECOScience
E
d
ition:
0
1
; La
st
upda
ted
: 201
1-
04-1
2
Top connected system tank, CS300
9.2
TABLE FOR RESISTANCE TEMPERATURE SENSOR
PT 100
You can check that the temperature sensors are functioning properly by
using the table below and an instrument for measuring resistance.
Temp °C
Resistance ohm
DR/Dt ohm/°C
-20
92.160
0.393
-10
96.086
0.392
0
100.000
0.391
10
103.903
0.390
20
107.794
0.389
30
111.673
0.387
40
115.541
0.386
50
119.397
0.385
60
123.242
0.384
70
127.075
0.383
80
130.897
0.382
90
134.707
0.380
100
138.506
0.379