Malfunction cause
Malfunction
code
Safeguard
Enter condition
Resume condition
Difference in water temp.
is higher than
〖
C5
〗
(sets)
in heating mode
Resetting Parameters
Expansion valve opening
is too small
Adjust thermal expansion
valve opening larger
Water flow is too small
Check the water-way valve
is fully open, or change the
water pump to increase
flow
Y# high pressure
malfunction
E1
:
3Y
the Y#
compressor
stopped
Heat exchanger fouling
Unit operation will have a
period of time scaling
phenomenon, cleaning
Expansion valve opening
is too small
Adjust thermal expansion
valve opening larger
System has a leak
Refrigerant leak detection
and re-filling
Y# low pressure
malfunction
E1
:
4Y
the Y#
compressor
stopped
Dust accumulation fin heat
exchanger
Unit run period of time will
produce dust phenomenon,
cleaning
Circuit board temperature
probe is not inserted well
or loose
Re-insert temperature
probe
Y# coil
temperature
malfunction
E1
:
6Y
the Y#
compressor
stopped
Temperature probe is
damaged
Replacement of the
corresponding temperature
probe