secondly,compressor run heating for the circulating water〖C8〗.
19). Compressor delay protection of the running and stop
In order to protect the compressor, After the compressor stopped,the unit is restart after
〖C9〗minutes.
When the compressor running, Normal it stopped after 〖CA〗minutes, Unless the
air-conditioning shutdown or malfunction.
20).(Compressor)high pressure protection: (high pressure Switch off last 〖CC〗 seconds)
in an hour less than 〖bE〗 times ,the compressor protected,when the pressure is restored ,
compressor will restart (meet 〖C9〗 minutes delay). In more than (〖bE〗 times per hour)
of fault the controller is locked, the compressor is no longer restart regardless of whether the
reset switch reset, and display the fault code.
21).(Compressor)low pressure protection:when the compressor start-up after〖Cb〗
minutes, then low pressure Switch begin detect,(low pressure switch off last 〖CC〗
seconds) in an hour less than 〖bE〗 times ,the compressor protected, during the period
of defrost, does not detect low pressure switch, when the pressure is restored , compressor
will restart (meet 〖C9〗 minutes delay). In more than (〖bE〗 times / hour) when the
controller of the fault is locked, the compressor is no longer restart regardless of whether the
reset switch reset, and display the fault code,then if you want to restart,it may disconnect
the power.
22). Water flow switch protection
After the circulating water pump run 30seconds,when the controller detects water
flow switch off more than 〖Cd〗seconds,turn off all load and water flow switch protection.