Safety Instructions and Warranty Terms
44
Manual econ sens+
Version 1.40
Technical data
econ sens+ basic unit
mechanical
Dimensions (W x H x D)
[mm]
94 x 23 x 121
Equipment class
IP 20
electrical
Operating voltage range
1
[V
AC
]
70..350 (betw. U1,U2,U3 and N)
Terminal cross-section
Voltage inputs
mm²
0.15 - 4 mm²
Max. clamping torque
Nm
2,5
Total internal consumption
[W]
max. 1.5 Watt with
Ethernet operation
Frequency range
Hz
45…65 Hz
Temperature range
°C
0..55°C, max. 80% rel H, non-
condensing 2000m NN
Rel. error Voltage measurement
%
+/- 1
1
The supply voltage is generated from phases L1 and L2 (with connection to 3-phasen power system)
S0 pulse outputs
Description
S0 pulse outputs in accordance
with DIN 43864
Voltage range
[V
DC
]
5..30
Max. load / Output
A
0.1
Max. pulse rate
Hz
10
Terminal cross-section
mm²
0.15 - 4 mm²
Max. clamping torque
Nm
2,5
Ethernet Interface
100Mbit fix via RJ-45 socket
Communications interface Modbus TCP
RS-485-Interface
Description
RS-485 based Bussystem.
1 Master and max. 31 Slaves
(Modbus RTU)
Max. cable length Master -> last Slave
m
1200 (Modbus)
Baudrate
Bd
9600, 19200, 38400, 57600,
115200 (Modbus)
Terminal cross-section
mm²
0,15 - 4 mm²
Max. clamping torque
Nm
2,5