Initial Operation
For initial operation of the econ sens+ proceed as follows:
1.)
Before you switch the device on, check that all cable connections to the econ sens + are
in place as described in the previous chapters.
2.)
Switch on the circuit breakers in the voltage path; all three indicator LEDs should then
light up.
Check that the voltages are applied to the device and that the phases L1, L2 and L3 are
correctly connected.
3.)
Access the web interface of the device and check first of all the time settings and the
display in the
Meter
menu
.
If there is no load connected you should at least see the voltage values. If there is a load
connected, verify the measurement result, if possible.
If you do not see any measured values even though there is a load connected, proceed
as described in Chapter 7
Troubleshooting
.