Modbus Pulses / s (S0/RS 485-Variante) submenu
The settings for the Modbus communication is carried out in this section.
Modbus Settings
The setup has to be performed via HTML.
Parameter
Description
Modbus Interface
This selects which modbus protocol is used:
- none
- Modbus TCP
- Modbus RTU (over RS485 line)
- Modbus Gateway
Modbus address
This single byte value selects the bus address.
Allowed values are 0..255.
Modbus baudrate
This selects the RS485 baudrate. Allowed values are 9600, 19200, 38400,
57600 and 115200.
Modbus paritiy
This selects the RS485 parity: none, odd, even.
Modbus stopbits
Stopbits: 1 or 2.
Modbus port number
This selects the port number for modbus over TCP/IP.
The default value is 502. Other values are allowed
Modbus TCP delay
This parameter is only used when the sesn+ is used as a modbus
gateway. This is a time in milliseconds, allowed values are 0..3600000.
Modbus RS 485 timeout
This parameter is only used when the sens+ is used as a modbus
gateway. This is a time in milliseconds, allowed values are 0..3600000.
Modbus Events Flag
minimum activity time (ms)
minimum activity time for modbus event flags, can be set via HTML
modbus settings. This is a time in milliseconds, allowed values are
0..3600000.
Figure 31:
Custom Modbus settings in the menu pulse / s (Example: Modbus TCP)