ecom-B
At the end of the measurement routine
(curser
<down>
) it is checked whether a
gas leakage at the unit could be deter-
mined. Confirmation could be done by us-
ing the key
<Enter>
(yes / no).
The printout (IR printer required) of all re-
sults of the measurement routine could be
done by pressing
<Print>
.
6.2.2. Oil fan burner
Using Heating oil (B) as fuel type the rou-
tine starts by determining the oil flow and
the thermal capacity brought to the boiler.
Open the menu
<Oil pressure>
by press-
ing
<Enter>
. Enter the measured oil pres-
sure as follows:
1. Use the keys
<store>
(left) and
<Print>
(right) to come to the positions which
should be changed (corresponding field is
flashing).
2. Set the number by using the curser
keys.
After setting and pressing
<Enter>
the sub-
menu nozzle size will be opened. Enter the
used nozzle size like described above.
After setting and pressing
<Enter>
the
result of the calculation will be displayed.
The calculation can be repeated if needed.
For calculation following heating values are
taken:
Heating oil (B) = 11,86 kWh/kg
Burn. w. blower
Gas leakage
No
Change :
↵
↵↵
↵
Burn. w. blower
Oil rate
- - . -
kg/h
Perfo.
- - . -
kW
Input :
↵
↵↵
↵
Burn. w. blower
Oil rate
2.5
kg/h
Perfo.
29.7
kW
Input :
↵
↵↵
↵
Burn. w. blower
Oil press.
1
2.00
bar
↑↓
↵
↵
↵
↵ ← →
Burn. w. blower
Nozz. size
0
.60
Gal/h
↑↓
↵
↵
↵
↵ ← →