Level / Pump control

The control box (12) is installed if the optional level sensor was added. The 
programmable LED display will show the tank level as a percentage of the sensor 
scale.  The LED display is used to control the unit start/stop. The will also stop the 
distribution pump from running dry when tank level is too low or signal is outside 
normal range.

There are 4 relays that control those functions. Relay 1 and 2 control the unit and 

relay 3&4 the pump. Relay 1 is set to 95% and will stop the HOCl 

production when reached. Relay 2 will start HOCl production when level goes below 50%. Relay 3 will stop the 
pump from running when level goes below 10%. Relay 4 will stop pump when level shows 101.5% which is outside 
normal operation.

The relay settings can be changed by the operator. Press the up or down arrow on the display when default screen 
is displayed to access “fast set-point”. Press up/down arrow to choose the wanted relay to change. Press the “ok” 
button to access the desired relay set-point. Relay 2 setpoint should always be lower than relay 1 setpoint. 

Pressing the “ok” button when default screen is display will prompt you for a password. Enter the password to 
change setup of the programmable LED unit.

Ultrasonic level sensor

The ultrasonic level sensor (14) connects to the control cox. The M12 connector used for 
the sensor can only be installed in one position, make sure the M12 connector is connect 
straight and all the way (do not use any tools). The ultrasonic level sensor is mounted to 
the HOCl storage tank, in a way that leaves a free line of sight to the measured liquid.

The sensor has a dead band of 300 mm, meaning that the sensor has to be minimum 
300 mm from the measured liquid. Maximum range of the default sensor is 3 meters.

The sensors signal strength is indicated on top of the sensor using a red LED. Make sure the red LED is on for the 
sensor to work correctly.

Distribution pump

The optional distribution pump is a constant pressure pump that uses a build in VFD. The pump uses a pressure 
sensor to measure the pumps output pressure. The pump speed is adjusted to maintain the correct pressure.

The pump connects to the Backboard control box with two cables. Cable 1 supply the needed power (Vac). The 
second cable is used for pump protection in specific situations.

The pump starts on its own when the pressure in the outlet line drops. The pump stops again when the pressure in 
the output line is higher than the setpoint. The pump pressure can be adjusted on the pump by pressing the arrows 
on the top. The storage tank is connected to the pump inlet and all consumers connect to the output.

Picture 18 Control box

Picture 19 Level sensor

Relay number

Description

Setting %

1

 

S

ystem is stopped at this setting

95

2

 

S

ystem is started at this setting

50

3

Pump is stopped, to avoid running dry

10

4

Pump is stopped as level signal is outside normal range

101.5

Summary of Contents for E-1200

Page 1: ...E 1200 System prebuilt with pH Control Installation OperationManual EcoloxTech Tel 1 954 900 6070 service ecoloxtech com ...

Page 2: ...w preventer 4 Water filter 4 Dosing unit 4 Holding tank 5 Pressure reduction valve 5 Flow control valve 5 Level pump control 5 Installation 6 6 6 7 7 7 7 8 8 8 9 9 9 System start up 10 Step by step 10 Calibrating the level sensor 11 Pump start up 11 Spare parts list 12 ...

Page 3: ...g units d Holding tank with float valve e Pressure reducer f Flow control 2 E 240 or 1200 unit 3 Control box Pump level g Level sensor 4 HOCl storage tank option not on picture 5 Distribution pump option not on picture 6 Brine tank option not on picture 6 shows location 7 Hydrochloric acid HCl connection Picture 1 Shows system components arrows shows flow direction ...

Page 4: ...sing unit c uses the waters pressure to mix in a concentrate The injection rate of the concentrate can be adjusted using the scale at the bottom of the unit The dose of concentrate will be directly proportional to the volume of water entering the unit regardless of variations in flow or pressure The ratio can be adjusted using the scale shown in picture 5 Make sure the locking ring at the bottom o...

Page 5: ... system The E 1200 E 240 system has a maximum allowed pressure of 50 psi This is to protect the internal parts of the system The pressure reduction valve e is pre adjusted from factory to 45 psi so no action is needed from the customer side Flow control valve The flow control valve f can adjust the flow though the system The flow can be adjusted to anything within the system flow range For the E 1...

Page 6: ...ndicate additives used in the process Process steps 1 Blue color The blue color is normal water before any changes are made The water inlet splits up into two separate streams The water that goes into dosing unit 3 is a low flow rate The main part of the water goes though dosing unit 5 2 Red color The red color indicates the addition of the purple product HCl The HCl is added to the water in dosin...

Page 7: ...r is lowered into the tank used for the brine Filter and additional hose is included in the system Additional information on the specific system can be found in the unit s manual E1200 unit https www ecoloxtech com pdf e1200soperationmanual pdf E240 unit http ecoloxtech com pdf e240soperationmanual pdf Power connection Depending on what options have been chosen the power is connected differently T...

Page 8: ...system using the hose in picture 14 The hose is run out though the hole in the bottom left side of the unit Avoid having height differences in system and brine tank location System pump cannot handle more that 2 3 meters height difference Try to keep the length of the brine hose at a minimum Hydrochloric Acid Hydrochloric Acid is connected at location 11 on picture 10 purple arrow The concentratio...

Page 9: ... only be installed in one position make sure the M12 connector is connect straight and all the way do not use any tools The ultrasonic level sensor is mounted to the HOCl storage tank in a way that leaves a free line of sight to the measured liquid The sensor has a dead band of 300 mm meaning that the sensor has to be minimum 300 mm from the measured liquid Maximum range of the default sensor is 3...

Page 10: ...ndle on the scale up lowers the pH level in the tank 4 10 When desired pH level is reached the hose at the bottom of tank 4 can be reattached 11 Let tank 4 fill with water at the correct pH level and make sure the float valve controls the level as intended 12 Adjust scale on dosing unit 5 to 50 half way 13 There are two different ways to do the next part a Run system b Disconnect water inlet 8 fro...

Page 11: ...we are outside the 3 meter range 2 Install the sensor in the desired location Make sure there are no edge the sensor can see If the sensor sees sharp edges the reading will be off 3 Push and hold the analog button for longer than 2 seconds Power LED off Output LED on 4 Hold a piece of cardboard at the position which equals 100 full tank 5 The red LED signal must be on of flashing 6 Click analog bu...

Page 12: ...e SKU T 1137 14 3 4 Insert x 3 4 MPT Adapter Elbow SKU P 1029 23 1 4 OD Silicone Tubing SKU T 1126 6 3 4 Socket PVC Union SKU P 4488 15 3 4 Reinforced Tubing 70 psi SKU T 1040 24 Foot Valve Strainer 1 4 OD SKU T 1026 7 3 4 Socket PVC 90 Degree Elbow Sch 40 SKU P 4510 16 3 4 Insert x 3 4 MPT Adapter SKU P 1028 25 Compact Float Valve Yellow Black SKU P 4519 8 3 4 Socket x Socket x FPT PVC Tee Sch 40...

Reviews: