![ECOCOACH ecoBatterySystem Technical Manual Download Page 15](http://html.mh-extra.com/html/ecocoach/ecobatterysystem/ecobatterysystem_technical-manual_2353979015.webp)
3
Product description
General data
Inverter (ecoInvert)
Charge/discharge capacity
max. 0.5 C-rate
Inverter (ecoInvert)
Efficiency
max. 96%
Inverter (ecoInvert)
Power
•
ecoInvert Studer Small: 12 kW
•
ecoInvert Studer Large: 24 kW
Cooling principle
Air-cooled
Cascading
•
Master/slave function
•
Earth fault and grid monitoring
•
AC short-circuit capability and electrically isolated connec-
tions
•
Leakage current monitoring
Operating modes
•
Mains operation
•
Compatible with emergency power supply (with additional
mains isolator switch)
•
Isolated operation with additional power system protec-
tion
External requirements
LAN connection, power connection (power outlet) for the
ecoFirewall mains adapter
Measurements
Separate for each connection (domestic grid, mains connec-
tion, photovoltaic system, charging station, electric boiler, etc.)
A virtual measuring point can also be set.
Display
Shows the battery charging status, operating mode, tempera-
ture, active error messages
ecoBatteryModule control
CAN bus
Battery capacity
1
•
ecoBatterySystem Small: max. 4 ecoBatteryModules, max.
26 kWh
•
ecoBatterySystem Large: max. 10 ecoBatteryModules,
max. 65 kWh
Floor loading
•
ecoBatterySystem Small: at least 300 kg / 0.5 m
2
•
ecoBatterySystem Large: at least 600 kg / 0.5 m
2
Protection class
IP20
Operating temperature range
0 °C to 40 °C
Humidity
5-80%. (non-condensing)
Standards and directives
•
CE
•
EN 61000-6-1:2007
•
EN 61000-6-3:2007 + A1:2011
•
EN 62477-1:2012
•
VDE-AR-N 4105 Application Guide: 2011-08
•
ÖVE/ÖNORM E 8001-4-712
Empty weight (without ecoBat-
teryModule)
With Studer inverter:
•
ecoBatterySystem Small: 228 kg
•
ecoBatterySystem Large: 324 kg
Control and optimisation
Using the ecocoach app
1
Information from LG Chem, gross capacity
TM_ecoBatterySystem_2.2_en-UK
11