4.1  SYSTEM ENCLOSURE INTERIOR LAYOUT DRAWING 

4.2  WIRING 
 
 
Line voltage power to system: 

Take caution when drilling holes for installing 

conduit connections to avoid damaging internal system components

. An input 

wiring terminal strip for line voltage (line and neutral) can be located at the top left 
corner of the circuit board. A ground stud is located on the metal  mounting plate 
directly beside this terminal strip. 

Reference minimum and maximum system 

voltage specifications on page-5 of this manual.

 

21 

7.7 SYSTEM PROGRAMMING -  RELAY OUTPUT CODES 
 

 

“3221” Relay Enable or Disable: 

This code allows the user to enable or disable 

any of the four system relays. To achieve this, input code “3221”, then depress 
push-button “3” for enable or “1” for disable. Depress push-button “2” to scroll to the 
next channel. Once this function is finished, continue to depress push-button “2” until 
you reach the last channel and the system will  automatically start to scroll through 
all “active” channels. 

 

 
 

Selection: “Yes or No”

 

 

 
 
“2311” Time Delay on “Make”: 

This code allows the user to set a time delay period 

before one or more relays are activated in the event of a gas alarm. There is no time 
delay available for a fault condition. To achieve this, input code “2311”, then depress 
push-button “3” to increment or “1” to decrement the time. Once this function is    
finished, continue to depress push-button “2” until you reach the last channel and 
the system will automatically start to scroll through all “active” channels. 
 
Note:  A  relay  assigned  to  activate  in  the  event  of  a  gas  alarm  will  activate            
immediately unless an off delay is programmed. If an off time delay has been      
programmed, the relay will deactivate after the off delay has expired. 

 
 
Selection: “0.0 to 10.0” minutes 
 
 

 

“2312” Time Delay on “Break”: 

This code allows the user to set a time delay    

period before each relay is deactivated. To achieve this, input code “2312”, then  
depress push-button “3” to increment or “1” to decrement the time. Once this      
function is finished, continue to depress push-button “2” until you reach the last 
channel and the system will automatically start to scroll through all “active” channels.  
 
Note: All time delays are +/- 6 seconds timing tolerance 
 

 
Selection: “0.0 to 10.0” minutes 
 
 

 

“2331” Setting Relay Gas Alarm Activation: 

This code allows the user to select 

the normal activation for each relay in the event of a gas alarm. To achieve this,  
input code “2331”, then depress push-button “3” to increment or “1” to decrement 
through the choices. Depress push-button “2” to scroll to the next channel. Once this 
function is finished, continue to depress push-button “2” until you reach the last 
channel and the system will  automatically start to scroll through all “active”       
channels.  
 

 
Selection: “Zone, All, None, Sens” 

RL   1    Menu    3221 
Enabled    ?       

RL   1   Menu     2311 
On Delay               0.0 

RL   1   Menu    2312 
Off   Delay            0.0 

RL    1    Menu   2331 
Normal  Act       Zone 

Summary of Contents for PAC-44 Series

Page 1: ...ENSORS INC PAC 44 SERIES PROGRAMMABLE GAS DETECTION CONTROLLER 1451 Old Pecos Trail Santa Fe NM 87505 4737 USA Ph 800 472 6626 fx 505 988 1315 www ecosensors com INSTALLATION OPERATION MANUAL REV D OC...

Page 2: ...2 27...

Page 3: ...bon Monoxide sen sors 8 0 REPLACEMENT PART NUMBERS PART NUMBER DESCRIPTON PAC 44 EN Fiberglass enclosure with Lexan label audible alarm silence PAC SPS Switching power supply PAC MCB Main circuit boar...

Page 4: ...crement to 1 to decrement the value to achieve 4 00 mA on your meter Depress push button 2 to scroll to the next channel Move only the positive meter lead to channel 2 and repeat the last step to once...

Page 5: ...o increment or 1 to decrement the value Depress push button 2 to scroll to the next channel Once this function is finished continue to depress push button 2 until you reach the last channel and the sy...

Page 6: ...continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection Fail Safe Yes or No Note The definition of F...

Page 7: ...croll through all active channels Selection 1 2 3 or 4 2113 Monitor Channel Number This code allows the user to assign the channel number the relay will monitor with regards to gas or fault alarms if...

Page 8: ...ion is finished continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Note A relay assigned to activate in th...

Page 9: ...el Once this function is finished continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection N A CH 1 Me...

Page 10: ...arm Set Point This code allows the user to select or change a high alarm set point for each channel To achieve this input code 1213 then depress push button 3 to increment or 1 to decrement the value...

Page 11: ...e to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection Asc or Desc 2213 High Alarm Ascending or Descending...

Page 12: ...solid state or catalytic sensor element It could also indicate an expired Oxygen sensor element from an integral Oxygen sensor or remote Oxygen sensor transmitter Alarms Upon detection of a gas conce...

Page 13: ...faster than the normal scroll rate The scroll pattern is from the most serious alarm condition to the lesser alarm condition Fault is considered to be the most serious alarm condition folowed by high...

Page 14: ...ding Descending 18 2212 Mid Alarm Ascending Descending 18 2213 High Alarm Ascending Descending 18 1211 Low Alarm Set Point 19 1212 Mid Alarm Set Point 19 1213 High Alarm Set Point 19 Input Channel Cal...

Reviews: