7.8 SYSTEM PROGRAMMING -  ANALOG OUTPUT CODES 
 

 

“3231” Output Channel Enable or Disable: 

This code allows the user to enable or 

disable any of the four system analog output channels. To achieve this, input code 
“3231”, then depress push-button “3” for enable or “1” for disable. Depress push-
button “2” to scroll to the next channel. Once this function is finished, continue to 
depress push-button “2” until you reach the last channel and the system will       
automatically start to scroll through all “active” channels.  

 
 
Selection: “Yes or No” 
 

 
 

“3112” Monitor Input Channel: 

This code allows the user to select the input   

channel each analog output channel will monitor. Each output can monitor only one 
input channel. To achieve this, input code “3112”, then depress push-button “3” to 
increment or “1” to decrement to the desired     channel. Depress push-button “2” to 
scroll to the next channel. Once this function is finished, continue to depress push-
button “2” until you reach the last channel and the system will automatically start to 
scroll through all “active” channels.  

 
 
Selection: “1, 2, 3 or 4” 
 

 

“1321” Setting Analog Output Low Range: 

This code allows the user to select the 

low range measurement for each channel. Default is 4.0 mA = “0”. This is a locked 
function. To achieve this, first input the software unlock code, then input code 
“1321”, then depress push-button “3” to increment or “1” to decrement the value. 
Depress push-button “2” to scroll to the next channel. Once this function is finished, 
continue to depress push-button “2” until you reach the last channel and the system 
will automatically start to scroll through all “active” channels.  

 
 
Selection: “0 to 1000” 
 
 

 

“1322” Setting Analog Output High Range: 

This code allows the user to select 

the high range measurement for each channel. Default is 20.0 mA = “full sensor 
measurement scale”. This is a locked function. To achieve this, first input the      
software unlock code, then input code “1322”, then depress push-button “3” to     
increment or “1” to decrement the value. Depress push-button “2” to scroll to the 
next channel. Once this function is finished, continue to depress push-button “2” until 
you reach the last channel and the system will automatically start to scroll through all 
“active” channels.  

 
 
Selection: “ 0 to 10,000” 
 

Note: Carbon Dioxide (CO2) is the only gas sensor type that provides a measure-
ment range selection from “0 to 50,000”. 

AC   1    Menu    3231 
Enabled   ?        Yes 

AC   1    Menu    3112 
Mon Channel           1 

AC   1    Menu    1321 
Range   Low            0 

AC   1    Menu    1322 
Range   High       200 

1.0  GENERAL 

 

 
The PAC-44 series systems are rugged, microprocessor based, programmable   
controllers  for  use  in  non-hazardous  (non-explosion  rated)  environments  for       
commercial and industrial applications. They can be configured for use with one to 
four remote analog transmitters. They can also be configured with one integral   
electrochemical sensor. 
 
A standard system provides an LCD digital display, a common set of LED indicating 
lights for fail, low, mid and high alarms, audible alarm with silence button, four     
analog inputs, four analog outputs and four dry contact relays. 
 
A large selection of “AST” series analog transmitters, utilizing electrochemical,   
catalytic, infrared and MOS (Metal Oxide Semiconductor) sensor elements, are 
available for use with this controller. 
 
 
 

2.0  SPECIFICATIONS 

 
 
Physical:                 a) Dimensions:  8.78” (223 mm) Wide  X  10.5” (267 mm) High X 
                                6.25” (159 mm) Deep 
 
                                b) Weight: 6.33 pounds (2.87 kg) 

 

Construction:          Water/dust  tight,  corrosion  resistant  fiberglass  with  hinged,        
                                secured door and Lexan door label 
 
Power:                     90 to 240 VAC, 47 to 63 Hz. 
 
Current Load:         Maximum allowable system current load is 1.36 Amps @ 24 VDC 
 
Relays:                    Standard: Four only S.P.D.T. dry contact relays rated 5 amps @ 
                                240 VAC each 
 
Output Signal:        Linear, analog 4 - 20 mA or 0 - 10 VDC, jumper selectable 
 
Visual:                     a)  Common  set  of  LED  indicating  lights  for:  Fault  Alarm  (red), 
                                Low  (Warning)  Gas  Alarm  (amber),  Mid  Gas  Alarm  (red),  High 
                                Gas Alarm (red) 
                                 
                                b) 16-character, two-line, back-lit LCD digital display 
 
                                c) Amber colored, LED light, relay coil status indicators (internal) 
 
                                d) Red colored, LED light “open loop” indicators for analog inputs 
                                and analog outputs (internal) 
 
 

Summary of Contents for PAC-44 Series

Page 1: ...ENSORS INC PAC 44 SERIES PROGRAMMABLE GAS DETECTION CONTROLLER 1451 Old Pecos Trail Santa Fe NM 87505 4737 USA Ph 800 472 6626 fx 505 988 1315 www ecosensors com INSTALLATION OPERATION MANUAL REV D OC...

Page 2: ...2 27...

Page 3: ...bon Monoxide sen sors 8 0 REPLACEMENT PART NUMBERS PART NUMBER DESCRIPTON PAC 44 EN Fiberglass enclosure with Lexan label audible alarm silence PAC SPS Switching power supply PAC MCB Main circuit boar...

Page 4: ...crement to 1 to decrement the value to achieve 4 00 mA on your meter Depress push button 2 to scroll to the next channel Move only the positive meter lead to channel 2 and repeat the last step to once...

Page 5: ...o increment or 1 to decrement the value Depress push button 2 to scroll to the next channel Once this function is finished continue to depress push button 2 until you reach the last channel and the sy...

Page 6: ...continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection Fail Safe Yes or No Note The definition of F...

Page 7: ...croll through all active channels Selection 1 2 3 or 4 2113 Monitor Channel Number This code allows the user to assign the channel number the relay will monitor with regards to gas or fault alarms if...

Page 8: ...ion is finished continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Note A relay assigned to activate in th...

Page 9: ...el Once this function is finished continue to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection N A CH 1 Me...

Page 10: ...arm Set Point This code allows the user to select or change a high alarm set point for each channel To achieve this input code 1213 then depress push button 3 to increment or 1 to decrement the value...

Page 11: ...e to depress push button 2 until you reach the last channel and the system will automatically start to scroll through all active channels Selection Asc or Desc 2213 High Alarm Ascending or Descending...

Page 12: ...solid state or catalytic sensor element It could also indicate an expired Oxygen sensor element from an integral Oxygen sensor or remote Oxygen sensor transmitter Alarms Upon detection of a gas conce...

Page 13: ...faster than the normal scroll rate The scroll pattern is from the most serious alarm condition to the lesser alarm condition Fault is considered to be the most serious alarm condition folowed by high...

Page 14: ...ding Descending 18 2212 Mid Alarm Ascending Descending 18 2213 High Alarm Ascending Descending 18 1211 Low Alarm Set Point 19 1212 Mid Alarm Set Point 19 1213 High Alarm Set Point 19 Input Channel Cal...

Reviews: