9
Eclipse Winnox Burner, WX Series, V2, Installation Guide 111, 2/26/2010
Gas Piping
Burner Piping
The burner is factory assembled and shipped as ordered.
NOTE:
If it is necessary to redirect piping, remove
the
outer four bolts only
X
. Rotate the rear cover and
replace bolts. When reassembling, be sure that:
• ratio regulator spring column
Y
is pointing up
• the bypass regulator spring column is pointing up
• arrow on the ratio regulator points in the direction of
gas flow
• integral fuel orifice and o-rings
Z
are reinstalled
• the same straight run of pipe
[
remains between
the ratio regulator and the burner.
Ŷ
Do not attempt to redirect piping by removing the
inner circle bolts
\
. Internal burner parts will be
damaged.
Figure 3.6 Burner Piping
Ŷ
Do not alter the bypass regulator. The NFPA
requires that the bypass regulator
]
be
appropriately vented and protected.
•
For applications in which the Winnox is
operating indoors, a vent limiting device is
installed in the bypass regulator.
•
For applications in which the Winnox is
operating outdoors, an insect/rain protector is
installed in the bypass regulator.
Supply Piping
Inlet pressure to the ratio regulator must stay within
specified limits. Refer to the appropriate Winnox
datasheet, series 111.
• Locate the valve train close to the burner. The gas
must reach the burner during the fixed trial for
ignition period.
• Sufficiently size the shut off valve in the valve train.
• Make sure piping is large enough to accommodate
flow required to meet burner input.
• Minimize piping elbows.
• Install fuel flow measurement device
X
upstream
from the burner inlet.
• If necessary to maintain inlet pressures to the
burner (see datasheet for your burner), install a gas
pressure regulator
Y
upstream of the burner inlet
and downstream of the valve train and fuel
measurement device
X
.
Figure 3.7 Supply Piping
Pipe Connections
Installation of a pipe union in the gas line is recommended
to simplify burner removal.
Use of flexible pipe is optional.
NOTE:
Flexible pipe causes higher pressure drops than
standard pipe. Consider this when sizing your gas lines.
CAUTION
CAUTION
T
a
p E
M
a
in
ga
s
shut-o
ff
v
a
lve tr
a
in