Modbus Read, Write and Override Parameters plus Exception Codes
8/05
UDC2500 Universal Digital Limit ControllerProduct
Manual
101
10.4.2 Limit
The identifying register addresses listed in Table 10-4 lists all the register addresses and
ranges or selections for the function parameters in Set-up Group Limit.
Table 10-4 Set-up Group Limit
Parameter
Description
Register
Address
Data
Access
Data Range or
Enumerated Selection
Hex
Decimal
High/Low Limit
0088
136
INT
R/W
0 = Low Limit
1 = High Limit
Power Up
Selections
0089 137
INT R/W
0 = Normal
1 = Reset
Limit Relay
Latched
00C4 196
INT R
0 = Not Latched
1 = Latched if in Limit Condition
Set Point Max
0007
7
FP
R/W
0 to 100% of PV
(Engineering Units)
Set Point Min
0008
8
FP
R/W
0 to 100% of PV
(Engineering Units)
Display 00B1
177
0 = PV
1= Set Point
Summary of Contents for UDC2500 Limit