Input Calibration
56
UDC2500 Universal Digital Limit ControllerProduct Manual
8/05
Calibration Steps
Use the following steps when calibrating an input.
Step
Action
1
Find the minimum and maximum range values for your PV input range from Table 5-1.
2
Disconnect the field wiring and find out what equipment you will need to calibrate.
3
Wire the calibrating device to your controller according to the set up wiring instructions
for your particular input (Subsection 5.4).
4
Follow the calibration procedure given for Input #1 (Subsection 5.5).
5.2 Minimum and Maximum Range Values
Select the Range Values
Calibrate the controller for the minimum (0 %) and maximum (100 %) range values of
your particular input type. Two input controllers will need to have each input calibrated
separately.
Select the Voltage, Current or Resistance equivalents for 0 % and 100 % range values
from Table 5-1. Use these values when calibrating your controller.
Table 5-1 Voltage, Milliamp and Resistance Equivalents for Input 1 Range Values
PV Input Range
Range Values
Sensor Type
°F
°C
0 %
100 %
Thermocouples
(per ITS-90)
B
0 to 3300
–18 to 1816
–0.100 mV
13.769 mV
E
–454 to 1832
–270 to 1000
–9.835 mV
76.373 mV
E (low)
–200 to 1100
–129 to 593
–6.472 mV
44.455 mV
0 to 1600
–18 to 871
–0.886 mV
20 to 900
–7 to 482
–
0.334 mV
20 to 550
–7 to 288
–0.334 mV
0 to 2400
–18 to 1316
–0.692 mV
–20 to 1200
–29 to 649
–1.114 mV
26.978 mV
K (low)
–20 to 750
–29 to 399
–1.114 mV
16.350 mV
NiMo-NiCo (NM90)
32 to 2500
0 to 1371
0.000 mV
71.773 mV
NM90 (low)
32 to 1260
0 to 682
0.000 mV
31.825 mV
Nicrosil-Nisil (Nic)
0 to 2372
–18 to 1300
–0.461 mV
47.513 mV
Nic (low)
0 to 1472
–18 to 800
-0.461 mV
28.455 mV
R
0 to 3100
–18 to 1704
–0.090 mV
20.281 mV