Troubleshooting/Service
8/05
UDC2500 Universal Digital Limit ControllerProduct
Manual
83
Procedure #6
Table 7-10 explains how to troubleshoot AuxiliaryProportional Output failure symptoms.
Table 7-10 Troubleshooting Auxiliary Output Failure
Step
What to do
How to do it
1
Make sure the controller is
configured for Auxiliary Output
and the proper range (4 to 20 or
0 to 20) is configured.
Make Options Set Up group function prompt
AUX OUT any selection other than NONE. If
this prompt does not show up, check if DIG IN
2 is enabled. If so, then as Auxiliary Ouptut
and Digital Input 2 are mutually exclusive, you
must chose which one of these features you
wish to use.
Make the Options Set UP group function
prompt CRANGE = 4–20 or 0–20 per your
application.
Refer to
Section 3 - Configuration
.
2
Check the field wiring.
Output impedance must be less than or equal
to 1000 ohms.
3
Check the output.
Change the AUX OUT selection to OUTPUT.
Put the controller into Manual mode and
change the output from 0 % to 100 % (4-20
mA). Use a DC milliammeter at the rear
terminals to verify the output.
4
Recalibrate the Auxiliary output. Refer to
Section 6 - Output Calibration
for
details.
5
Change Auxiliary Output board. Installation instructions provided with new
board.
6
Change Controller