Firmware V6.6.9
29.07.2020
115/147
The screen contains the following parameters:
Alarm signalling time ranges
Entry
Default
Start
Week timer start
00:00..23:59
08:00
End
Week timer end
00:00..23:59
16:00
XXXXXXXXX
Weekdays and groups of days
Mon-Fri
Mon-Sat
Mon-Sun
Sat-Sun
Mon, Tue, Wed,
Thu, Fri, Sat, Sun
Mon - Fri
Special days
Up to 30 special days on which the Service Centre is not manned can be defined using this entry screen. New
special days are defined using the button for editing.
The screen contains the following parameters:
Special days alarm signalling
Entry
Default
Entry screen for date
The input is made as follows: D/M or DD/MM
(day/month)
A special day can be deleted / removed again
with the entry of
"--" or "0:0" or "00:00".
1/1 ..31/12
--,0:0, 00:00
-
Provider
The telephone providers (e.g. D2, EPlus,…) for the SMS destinations are defined using this entry screen.
The screen contains the following parameters:
Alarm signalling provider 1/2
Entry
Default
Description
Description of the provider 1/2 e.g. "D2"
Max. 19 characters
-
Telephone number
Telephone number of the provider 1/2
-
Protocol
SMS protocol of the provider 1/2
NOTE: This must be requested from the
provider!
TAP, UCP
TAP
Other
The mode of operation of the multi-function relay AUX is configured using this entry screen. For further
information, see chapter Modem hardware reset, page 46.
The screen contains the following parameters:
If no time ranges are specified, the Service Centre is considered as not manned!
If no days are specified, the Service Centre is considered as always manned!
An alternative destination with a different telephone number and a different provider should always be
used for every destination! It is not ensured after successful transmission of any message to the
provider that this reaches the recipient promptly or at all. For this reason, alarm signalling only by SMS
should not be used and another separate alarm path should be implemented.