Firmware V6.6.9
29.07.2020
42/147
•
•
•
•
WDOG
: OFF -
MUST
always be set to OFF
BOOT
: OFF -
MUST
always be set to OFF
6.2 DIN rail mounting - SIOX Extension Module
SIOX Extension Module: without manual control switch / with manual control switch
A maximum of 4 SIOX (
S
erial
IO
E
x
tension) extension modules can be connected to the system centre. Each
SIOX module extends the system centre by an additional 12 digital inputs and 8 relay outputs. The number of
connected SIOX modules must be parameterised in menu 4-1-1.
The SIOX modules are available in two versions:
without manual control switch
with manual control switch to be able to switch the relay outputs manually (see chapter
)
The modules are connected to the system centre via SIOX power supply cables and SIOX data cables; see
chapter
SIOX - connection to the system centre
.
6.2.1 SIOX - connection to the system centre
The individual SIOX extension modules are supplied with power from the controller via the terminals 91-95
(SIOX-SUPPLY) and connected to each other in series via SIOX data cables (SIOX OUT and SIOX IN using
RJ45).