20
Network Cabling and Connection
Performance Characteristics and Cabling
For performance characteristics and cabling information, refer to the sources of
. The specifications shown in
are provided for convenience only and are not intended to be comprehensive.
Table 9
. Module Performance Summary
Module
Cable Distance
Number of
Nodes
Information Sources
FT 5000,
TP/FT-10,
TP/FT-10F
Bus: 2700 m (8850 feet)
worst case with Belden
®
85102 cable
Free topology: 500 m
(1640 feet) worst case
with Belden 85102 cable
and with no repeaters
(1000 m [3280 ft] total
wire with one repeater)
64 at -40 to +85 °C
•
Series 5000 Chip Data
Book
(005-0199-01)
•
FTT-10 User's Guide
(078-
0114-01)
•
FTT-10A User's Guide
(078-0156-01)
•
LPT-10 User's Guide
(078-
0105-01)
•
Control Module Data
Sheet (003-0121-01)
TP/XF-78,
TP/XF-78F
Bus: 1400 m (4600 feet)
worst case with 3 m (10
feet) stubs with 22
AWG (0.65 mm) Level
IV Cable
64 at 0 to +70 °C
44 at -40 to +85 °C
•
TPT User's Guide
(078-
0025-01)
•
Control Module Data
Sheet (003-0121-01)
TP/XF-1250
Bus: 130 m (430 feet)
worst case with 0.3 m (1
foot) stubs with 22
AWG (0.65 mm) Level
IV Cable, or Category 5
or 6 cable
64 at 0 to +70 °C
32 at -20 to +85 °C
16 at -40 to +85 °C
Control Module Data Sheet
(003-0121-01)
Notes
:
1.
Worst case distance figures are based on variations in device distribution,
device temperature, device voltage, wire characteristics, and FT 5000
Smart Transceiver or Neuron Chip characteristics, and allow for an
average wire temperature of up to +55 °C.
2.
Network length for TP/FT-10 channel varies by wire type.
Free Topology TP/FT-10 and TP/FT-10F
The following sections describe the wire characteristics and cabling terminations
for Free Topology TP/FT-10 channels. The FT 5000 Control Module and the
Neuron 3150 TP/FT-10 and TP/FT-10F Control Modules use a Free Topology
TP/FT-10 channel.
Summary of Contents for LONWORKS FT 5000
Page 1: ...LONWORKS Twisted Pair Control Module User s Guide 078 0015 01F...
Page 18: ...10 Mechanical Considerations Figure 5 Neuron 3150 Control Module Mechanical Footprint...
Page 20: ...12 Mechanical Considerations Figure 8 Vertical Component Profile for the Control Modules...
Page 22: ......
Page 26: ......
Page 34: ......
Page 55: ...www echelon com...