When ZERO OFF=YES, this setting is used to inhibit the LO ALRM condition when the unit is
reading 0. This is dependent on the low limit setting.
Set alarm RESET. AUTO will clear once the alarm is not active. MANUAL requires user to clear
alarm by depressing the ESC key, or for RS485 (GTC116) output, write 0 to corresponding
alarm BACnet object or Modbus register. Alarm will only clear when alarm is not active.
O
O
*HI ALRM=OFF
SET HI ALRM?
HI ALRM=OFF
Enable/disable HI alarm.
LO ALRM=OFF
Enable/disable LO alarm.
*LO ALRM=OFF
ALARM
HI ALRM=ON
*ALRM UM=AFPM
SET ALRM UM?
ALRM UM=AFPM
Set alarm units of measure to FPM or CFM (Note: A if ACT or S if STD measurement prefix set
by AIRFLOW= setting above).
LO ALRM=ON
SET LO ALRM?
ALRM UM=ACFM
*SETPNT=0
SET SETPNT?
SETPNT=0
Enter setpoint for alarm.
*TOL=10%
SET TOL?
TOL=10%
Enter tolerance as value above or below alarm setpoint. Units based on ALARM UM.
*DELAY=2 min
SET DELAY?
DELAY=2 min
Set alarm DELAY.
SET ZERO OFF?
ZERO OFF=NO
ZERO OFF=YES
*RESET=AUTO
SET RESET?
RESET=AUTO
*ZERO OFF=NO
RESET=MANUAL