5.4
Factory
Default
Menu
Settings
for
GP1
Sensor
Probes
The
GTC116
transmitter
is
“plug
and
play”
and
does
not
require
setup
unless
a
network
option
is
selected
that
requires
configuration.
Table
5
shows
the
factory
default
settings
for
all
compatible
sensor
probes.
To
change
the
Factory
Default
Settings,
see:
CHANGING
FACTORY
DEFAULT
SETUP
MENU
SETTINGS.
Display
Description
I-P
S.I.
AIRFLOW=
Airflow measurement method, Actual or Standard.
ACT
ACT
*LCDU/M=
Airflow units of measure
ACFM
LPS
*AREA=
Free area where station is located (required for volumetric measurement)
0.00 sq.ft.
(see note)
0.000 sq.meters
(see note)
*AO1 SGNL=
Output 1 signal type voltage or mA (airflow)
mA
mA
*AO1 UM=
Output 1 units of measure
AFPM
MPS
*AO1 FS=
Output 1 signal full scale
5,000 FPM
25 MPS
*LLIMIT=
Low limit cutoff
0 AFPM
0 MPS
*FLOW ADJ=
Output 1 Offset-Gain On/Off
Off
Off
*GAIN=
Output 1 Gain factor
1.000
1.000
*OFF=
Output 1 Offset factor
0.000
0.000
*TEMP METH=
Temperature Averaging
Weighted Avg.
Weighted Avg.
*AO2 SGNL=
Output 2 signal voltage or mA (temperature or alarm)
mA (see alarms) mA (see alarms)
*AO2 MS=
Output 2 signal minimum scale
-20º F
-30º C
*AO2 FS=
Output 2 signal full scale
160º F
70º C
*LCD INTG=
Number of flow calculations to be averaged for LCD display.
100
100
*AO1 INTG=
Number of flow calculations to be averaged for AO1 output.
30
30
*EB-LK INT=
Number of flow calculations to be averaged for EB-Link readings.
300
300
*ALT=
Altitude for flow correction relative to mean sea level (0 ft).
0 ft
0 m
*AO2 ASGN =
*AO2 ASGN = TEMP Output 2 Assigned Type is Temperature
TEMP
TEMP
*SETPNT=
Alarm setpoint value. For AO2 ASGN=ALARM , operates in conjunction
with TOL=value.
0
0
*TOL=
Alarm range tolerance value. For AO2 ASGN=ALARM , this setting
establishes the alarm range relative to the SETPNT= value.
10% 10%
*NO FAULT=
Sets the AO2 normal (not alarm) output state relative to the full scale
analog output selected. HI provides maximum full scale under normal
conditions and minimum scale during alarm. LO provides minimum full
scale under normal conditions and maximum scale during alarm.
HI
HI
*DELAY=
Time that the alarm condition must exist before alarm output is activated.
2 minutes
2 minutes
*ZERO OFF =
Set to YES to inhibit LO alarm condition when flow reading is below
LLIMIT= setting. Set to NO to disable this feature.
NO NO
*RESET =
Set to AUTO to have alarm self-clear when alarm condition no longer
exists. Set to MANUAL to require manual reset of alarm.
AUTO AUTO
Note: For GP1 probes, area is stored in one-wire, but can be changed.
Table
5. Factory
Default
Menu
Settings