11
G
OLD
S
ERIES
GTC116 T
RANSMITTER
a measurable difference!
EBTRON
IG
_GTC
116_R
3
A
Function
Address
Type
Units
Description
Range/Value
2
10001
boolean
Trouble Status
0:OK, 1:Trbl
4
30001-30002
float
FPM Average Airflow
0 to 15,000
4
30003-30004
float
°F
Average Temperature
-20 to 160
4
30005
word
Number of Inserts
0 to 16
4
30006
word
0
4
30007
word
Alarm Status
0: No alarm
1: High Alarm
2: Low Alarm
3: Both
4
30008
word
Connector C1 Sensors
0 to 8
4
30009
word
Connector C2 Sensors
0 to 8
4
30010
word
Connector C3 Sensors
0 to 8
4
30011
word
Connector C4 Sensors
0 to 8
4
30012-30043
float
FPM
Airflow Flow Traverse
0 to 15,000
30012-30013
Insert 1 Flow
↕
↕
30042-30043
Insert 16 Flow
4
30044-30075
float
°F
Temperature Traverse
-20 to 160
30044-30045
Insert 1 Temp
↕
↕
30074-30075
Insert 16 Temp
4
30076-30077
float
Sq.Ft. Area
0 to 100
4
300202
word
Float word order
0: high word first;
1: low word first
Analog Values
AV, 1
Area
sq.ft.
AV, 2
Traverse Data Status
0=None, 1=Flow,
2=Temp, 3=Both
AV, 3
Flow Traverse
FPM
↕
↕
↕
AV, 18 Flow Traverse
FPM
AV, 19 Temperature Traverse
°F
↕
↕
↕
AV, 34 Temperature Traverse
°F
Notes:
1. Flow and Temp traverse must be enabled through AV2.
2. User Executed Services Supported:
Subscribe COV, Read Property, Write Property,
Device Communication Control, Who-Is.
Analog Inputs
Type, ID
Name
Default
Units
Device GTC116
AI, 1
Average Flow
CFM
AI, 2
Average Temperature
°F
AI, 3
Alarm Status
0: No alarm,
1: High Alarm,
2: Low Alarm,
3: Both
Table
2. GTC116
BACnet
Objects
List
Table
3. GTC116
Modbus
Register
Map
BACnet
MS/TP