Ebtron GTC116 Installation Manual Download Page 15

 

 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 

15

 

 

  

G

OLD 

S

ERIES 

GTC116 T

RANSMITTER

 

a measurable difference! 

EBTRON 

IG

_GTC

116_R

3

A

 

5.6

 

GTC116

 ‐ 

Alarm

 

Features

 

Analog

 

output

 

AO2

 

(OUT2)

 

can

 

be

 

assigned

 

to

 

function

 

as

 

an

 

alarm

 

output.

 

The

 

AO2

 

alarm

 

output

 

can

 

be

 

assigned

 

in

 

the

 

SETUP

 

menu

 

to

 

operate

 

as

 

an

 

average

 

alarm

 

(A02

 

ASGN=ALRM)

 

or

 

as

 

a

 

trouble

 

alarm

 

(AO2

 

ASGN=TRBL)

 

for

 

monitoring

 

the

 

status

 

of

 

the

 

transmitter

 

and

 

sensors.

 

The

 

AO2

 

ASGN=

 

setting

 

is

 

located

 

in

 

the

 

ANALOG

 

OUT

 

submenu

 

of

 

the

 

SETUP

 

menu.

 

The

 

transmitter

 

LCD

 

display

 

will

 

indicate

 

the

 

Alarm

 

status

 

for

 

2

 

seconds,

 

and

 

will

 

cycle

 

through

 

any

 

other

 

alarms

 

if

 

multiple

 

alarm

 

events

 

are

 

active

 

for

 

2

 

seconds

 

each,

 

and

 

then

 

display

 

the

 

current

 

actual

 

flow

 

for

 

2

 

seconds.

 

Detailed

 

set

 

up

 

of

 

the

 

Alarm

 

features

 

is

 

shown

 

in

 

the

 

Setup

 

menu.

 

5.6.1

 

Average

 

Alarm

 

(AO2

 

ASGN=ALRM)

 

AO2

 

output

 

is

 

assigned

 

as

 

an

 

average

 

airflow

 

alarm

 

output.

 

Useful

 

for

 

applications

 

where

 

a

 

low

 

flow

 

alarm

 

or

 

a

 

high

 

flow

 

alarm

 

for

 

operation

 

outside

 

of

 

a

 

defined

 

range

 

(setpoint

 

and

 

tolerance)

 

is

 

required.

 

5.6.2

 

Trouble

 

Alarm

 

(AO2

 

ASGN=TRBL)

 

AO2

 

output

 

is

 

assigned

 

as

 

a

 

transmitter

 

trouble

 

alarm

 

indicating

 

a

 

fault

 

within

 

the

 

transmitter

 

or

 

a

 

sensor

 

of

 

the

 

airflow

 

measurement

 

system.

 

The

 

transmitter

 

LCD

 

will

 

indicate

 

a

 

trouble

 

code

 

and

 

a

 

brief

 

description

 

of

 

the

 

trouble.

 

Contact

 

EBTRON

 

customer

 

service

 

for

 

additional

 

information

 

or

 

assistance

 

with

 

trouble

 

codes.

  

5.6.3

 

No

 

Fault

 

(NO

 

FAULT=HI)

 

When

 

AO2

 

output

 

is

 

assigned

 

as

 

an

 

alarm,

 

this

 

setting

 

configures

 

the

 

normal

 

output

 

condition

 

to

 

be

 

HI

 

or

 

LO

 

relative

 

to

 

the

 

full

 

scale

 

analog

 

output

 

level

 

selected

 

when

 

no

 

fault

 

condition

 

exists.

 

5.6.4

 

Alarm

 

Indications

 

Table

 

6

 

details

 

the

 

alarm

 

types,

 

LCD

 

indications

 

and

 

AO2

 

alarm

 

output

 

indication.

 

User

 

can

 

select

 

either

 

or

 

both

 

of

 

the

 

two

 

Average

 

Alarms

 

or

 

the

 

Trouble

 

Alarm.

 

5.6.5

 

Low

 

Alarm

 ‐ 

“LO

 

ALRM=

 

ON”

 

The

 

Low

 

Alarm

 

is

 

activated

 

when

 

the

 

average

 

airflow

 

falls

 

to

 

a

 

defined

 

level

 

below

 

the

 

SETPNT=

 

value.

  

The

 

defined

 

level

 

is

 

equal

 

to

 

the

 

SETPNT=

 

value

 

minus

 

the

 

calculated

 

value

  

of

 

(TOL=

 

value

 

*

 

SETPNT=

 

value).

 

Once

 

active,

 

the

 

alarm

 

can

 

be

 

cleared

 

when

 

the

 

average

 

airflow

 

rises

 

above

 

the

 

set

 

point

 

minus

 

calculated

 

tolerance

 

value.

 

5.6.6

 

High

 

Alarm

 ‐ 

“HI

 

ALRM=

 

ON”

 

The

 

High

 

Alarm

 

is

 

activated

 

when

 

the

 

average

 

airflow

 

rises

 

above

 

a

 

defined

 

level

 

above

 

the

 

SETPNT=

 

value.

 

The

 

defined

 

level

 

is

 

equal

 

to

 

the

 

SETPNT=

 

value

 

plus

 

the

 

calculated

 

value

 

of

 

(TOL=

 

value

 

*

 

SETPNT=

 

value).

 

Once

 

active,

 

the

 

alarm

 

can

 

be

 

cleared

 

when

 

the

 

average

 

airflow

 

falls

 

below

 

the

 

set

 

point

 

+

 

calculated

 

tolerance

 

value.

 

5.6.7

 

Trouble

 

Alarm

 ‐ 

“AO2

 

ASGN=TRBL”

 

The

 

Trouble

 

alarm

 

provides

 

trouble

 

codes

 

useful

 

for

 

isolating

 

setup

 

issues

 

or

 

problems

 

within

 

the

 

transmitter

 

or

 

sensors.

 

The

 

transmitter

 

LCD

 

will

 

indicate

 

TROUBLE!

 

regardless

 

of

 

whether

 

AO2

 

is

 

assigned

 

to

 

TRBLE.

 

The

 

Diagnostic

 

submenu

 

can

 

be

 

engaged

 

for

 

the

 

error

 

code

 

and

 

a

 

brief

 

description

 

of

 

the

 

trouble.

 

Contact

 

EBTRON

 

customer

 

service

 

for

 

information

 

on

 

troubleshooting

 

using

 

the

 

Trouble

 

error

 

codes.

 

 

 

 

 

Table

 

6.

 

GTC116

 

Alarm

 

Types

 

and

 

Notifications

ALARM OUTPUT 

ASSIGNMENT TYPE 

LOCAL LCD DISPLAY OF ALARM 

TYPE AND NOTIFICATION

ANALOG OUTPUT 2 

ALARM INDICATION

NETWORK

ALARM INDICATION

**LOW ALARM**

(Average Alarm)

Display alternates between 

**LOW 

ALARM**

 (then any other alarms) and 

actual reading for 2 seconds each.

**HIGH ALARM**

(Average Alarm)

Display alternates between 

**HIGH 

ALARM**

 (then any other alarms) and 

actual reading for 2 seconds each.

TROUBLE !

(Trouble Alarm)

Display indicates 

TROUBLE ! 

(Refer to DIAGNOSTIC menu to obtain a 
brief description of the error and any 
other alarms).

On alarm or trouble, OUT2 is 
active high (or active low) 
relative to the full scale 
maximum (or minimum) 
analog value as determined 
by the SETUP Menu “NO 
FAULT=” selection. Individual 
sensor velocities can be 
viewed using the Diagnostics 
submenu.

Alarm Status is available at 
BACnet Objects and 
Modbus Registers.  Refer to 
BACnet Objects List and 
Modbus Register Map for 
additional detail.

Summary of Contents for GTC116

Page 1: ...th Combination RS 485 Network Output and Dual Analog Output Document Name IG_GTC116_R3B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse approve or tes...

Page 2: ...RT UP INITIALIZATION AND SETUP MENUS 12 5 1 Changing the System of Units IP or SI Units 12 5 2 GTC116 Transmitter Calibration 12 5 3 GTC116 LCD Display Notifications 12 5 4 Factory Default Menu Settin...

Page 3: ...ype B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTC116 Combination Analog RS 485 Transmitter Interior Detail 8 Figure 7 Sensor Addressing and Probe Positioning Detail 1...

Page 4: ...50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all connec...

Page 5: ...LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable receptac...

Page 6: ...mum VA Req 1 12 5 14 9 17 13 19 2 13 6 15 10 17 14 19 3 13 7 15 11 18 15 20 4 14 8 16 12 18 16 20 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input ter...

Page 7: ...here will be the potential for water runoff or condensation along the sensor probe cable s Sensor probe cable plugs are keyed as shown below Line up plug with receptacle and push straight on to recept...

Page 8: ...in the OFF position Connect signal wires for airflow rate and temperature or alarm to the small three position output terminal labeled OUTPUT on the upper left hand side of the main circuit board as s...

Page 9: ...mination switch set for No termination which is the recommended setting for devices installed on the network bus anywhere EXCEPT at the ends of the bus segment EBTRON recommends the following terminat...

Page 10: ...transmitter default baud rate for MS TP is 76 800 and for MODBUS is 19 200 Baud rate can be configured in the NETWORK sub menu Appendix A 4 3 5 GTC116 Setting Modbus Parity When using Modbus communica...

Page 11: ...Flow Traverse 0 to 15 000 30012 30013 Insert 1 Flow 30042 30043 Insert 16 Flow 4 30044 30075 float F Temperature Traverse 20 to 160 30044 30045 Insert 1 Temp 30074 30075 Insert 16 Temp 4 30076 30077...

Page 12: ...nu Note that Setup Menu items are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 4 IP System of Units Descriptio...

Page 13: ...s AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70 C LCD INTG Number of flow calculations to be averaged for LCD display 100 100 AO1 INTG Number of flow calcul...

Page 14: ...the SETUP menus 5 5 5 Changing the LCD Display from Volumetric Flow CFM to Velocity FPM The GTC116 transmitter is shipped from the factory to indicate volumetric flow To display velocity in FPM enter...

Page 15: ...ALRM ON The Low Alarm is activated when the average airflow falls to a defined level below the SETPNT value The defined level is equal to the SETPNT value minus the calculated value of TOL value SETPN...

Page 16: ...and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain the selected until the ESC button is pressed and norm...

Page 17: ...ing information for individual sensor data 5 8 3 Sensor Addressing and Probe Positioning Sensors are automatically addressed after power is applied to the transmitter as follows The probe connected to...

Page 18: ...rement to Standard units SFPM SCFM AIRFLOW ACT Custom LCD Flow Text Blinking prompt at position of the selected character Character is selected using the up and down arrows and then ENTER to accept an...

Page 19: ...t SW2 PCB switch setting VDC or mA for AO2 Pressing enter displays SET SW2 ON PCB prompt to confirm SW2 PCB setting AO2 output is assigned as an airflow alarm output Refer to ALARM settings part 4 AO2...

Page 20: ...eft Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and ESC to move to left Set BACnet IP or Ethernet protocol SET IP SET NETADDRESS NETWORK IP 10 0 0...

Page 21: ...responding alarm BACnet object or Modbus register Alarm will only clear when alarm is not active O O HI ALRM OFF SET HI ALRM HI ALRM OFF Enable disable HI alarm LO ALRM OFF Enable disable LO alarm LO...

Page 22: ...2 TEST SET OUT2 TEST OUT2 TEST 0 OUTPUT TEST FIELD ADJUST RUN FA WIZARD SET FAW INT FAW INT 300 ADJUSTMENTS OFF 0 SET OFF OUT1 TEST SET OUT1 TEST OUT1 TEST 0 FLOW ADJ ON GAIN 1 000 SET GAIN GAIN 1 000...

Page 23: ...YES Displays active trouble codes and their descriptions Contact EBTRON customer service for recommended service information Set DSBL TRBL YES to ignore currently displayed TRBL alarm To disable all...

Page 24: ...T SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS CONTROL INTERFACE OUT 2 can be set for analog Temperature Alarm or Trouble output Alarm output can be set as active high or...

Reviews: