Ebtron GTC116 Installation Manual Download Page 19

 

 

EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 

19

 

 

  

G

OLD 

S

ERIES 

GTC116 T

RANSMITTER

 

a measurable difference! 

EBTRON 

IG

_GTC

116_R

3

A

 

 

FROM PART 1

Analog cards only

if AO1 SGNL=mA

if AO1 SGNL=VDC

AO2 output is assigned as temperature output.

if AO2 SGNL=mA

if AO2 SGNL=VDC

if AO2 CFG=TEMP

if AO2 CFG=ALRM or TRBL

TO PART 3

NO FAULT = HI

Set AO1 output units to FPM or CFM.  (Note: A-ACT or 
S-STD measurement is set by AIRFLOW= setting above).

*AO2 MS=-20

SET AO2 MS?

AO2 MS=-20

*AO2 FS=160

AO2 RNGE=0-5

*AO2 UM=F

AO2 UNITS FIXED

The text "AO2 UNITS FIXED" flashes to indicate that this setting is fixed and cannot be 
modified.

*NO FAULT = HI

SET NO FAULT?

NO FAULT = LO

AO2 RNGE=FIXED

The text "AO2 RNGE=FIXED" flashes to indicate that this setting is fixed and cannot be 
modified.

*AO2 RNGE=0-10

SET AO2 RNGE?

AO2 RNGE=0-10

Set analog output range (VDC) for AO2.

SET AO2 FS?

Integration samples.  Also same as network integration.

*AO2 ASGN=TEMP

SET AO2 ASGN?

AO2 ASGN=TEMP

AO2 ASGN=ALRM

*A02 SGNL=mA

SET SW2 ON PCB

Display initially shows the current SW2 PCB switch setting (VDC or mA) for AO2.  Pressing 
enter displays "SET SW2 ON PCB" prompt to confirm SW2 PCB setting.

AO2 output is assigned as an airflow alarm output. 
Refer to ALARM settings (part 4).

AO2 FS=160

*AO1  FS=5000

SET AO1 FS?

AO1 FS=5000

AO2 ASGN=TRBL

*AO1 INTG=30

SET AO1 INTG?

AO1 INTG=30

SET AO1 RNGE?

Set analog output range (VDC) for AO1.

AO1 RNGE=0-10

AO1 RNGE=0-5

*AO1 UM=AFPM

SET AO1 UM?

*A01 SGNL=mA

SET SW1 ON PCB

Display initially shows the current SW1 PCB switch setting (VDC or mA) for AO1.  Pressing 
enter displays "SET SW1 ON PCB" prompt to confirm SW1 PCB setting.

*AO1 RNGE=4-20

AO1 RNGE=FIXED

The text "AO1 RNGE=FIXED" flashes to indicate that this setting is fixed and cannot be 
modified.

The text "AO1 ASGN FIXED" flashes to indicate that this setting is fixed and cannot be 
modified.

ANALOG OUT

*AO1 ASGN=FLOW

AO1 UM=AFPM

AO1 ASGN FIXED

AO2 output is assigned as a transmitter trouble alarm indicating that a sensor or transmitter 
fault has occurred.

Sets AO2 alarm/trouble output state when no fault condition is present, expressed as HI (full 
scale analog output) or LO (minimum scale analog output).

AO1 UM=ACFM

Set full scale for AO1. FS default value is dependent on probe type connected.

O

*AO1 RNGE=0-10

*AO2 RNGE=4-20

O

Set AO2 minimum scale.

Set AO2 full scale.

Summary of Contents for GTC116

Page 1: ...th Combination RS 485 Network Output and Dual Analog Output Document Name IG_GTC116_R3B a measurable difference EBTRON BACnet is a registered trademark of ASHRAE ASHRAE does not endorse approve or tes...

Page 2: ...RT UP INITIALIZATION AND SETUP MENUS 12 5 1 Changing the System of Units IP or SI Units 12 5 2 GTC116 Transmitter Calibration 12 5 3 GTC116 LCD Display Notifications 12 5 4 Factory Default Menu Settin...

Page 3: ...ype B Transmitter Connector Panel Detail 7 Figure 5 Connector Detail 7 Figure 6 GTC116 Combination Analog RS 485 Transmitter Interior Detail 8 Figure 7 Sensor Addressing and Probe Positioning Detail 1...

Page 4: ...50 8 mm to each side and 3 5 in 88 9 mm below the transmitter to allow for cover removal sensor connections and heat dissipation Locate the transmitter in a location that can be reached by all connec...

Page 5: ...LCD contrast Transmitter status LED Green 1 second flash normal 2 second flash for fault High accuracy A D converter Gold plated interconnects to optional output cards Positive locking cable receptac...

Page 6: ...mum VA Req 1 12 5 14 9 17 13 19 2 13 6 15 10 17 14 19 3 13 7 15 11 18 15 20 4 14 8 16 12 18 16 20 3 2 Connecting Power to the Transmitter Connect 24 VAC power to the large two position power input ter...

Page 7: ...here will be the potential for water runoff or condensation along the sensor probe cable s Sensor probe cable plugs are keyed as shown below Line up plug with receptacle and push straight on to recept...

Page 8: ...in the OFF position Connect signal wires for airflow rate and temperature or alarm to the small three position output terminal labeled OUTPUT on the upper left hand side of the main circuit board as s...

Page 9: ...mination switch set for No termination which is the recommended setting for devices installed on the network bus anywhere EXCEPT at the ends of the bus segment EBTRON recommends the following terminat...

Page 10: ...transmitter default baud rate for MS TP is 76 800 and for MODBUS is 19 200 Baud rate can be configured in the NETWORK sub menu Appendix A 4 3 5 GTC116 Setting Modbus Parity When using Modbus communica...

Page 11: ...Flow Traverse 0 to 15 000 30012 30013 Insert 1 Flow 30042 30043 Insert 16 Flow 4 30044 30075 float F Temperature Traverse 20 to 160 30044 30045 Insert 1 Temp 30074 30075 Insert 16 Temp 4 30076 30077...

Page 12: ...nu Note that Setup Menu items are shown in IP System Of Units When SI System of Units is selected the units of measure abbreviations used in the menus is shown in Table 4 IP System of Units Descriptio...

Page 13: ...s AO2 MS Output 2 signal minimum scale 20 F 30 C AO2 FS Output 2 signal full scale 160 F 70 C LCD INTG Number of flow calculations to be averaged for LCD display 100 100 AO1 INTG Number of flow calcul...

Page 14: ...the SETUP menus 5 5 5 Changing the LCD Display from Volumetric Flow CFM to Velocity FPM The GTC116 transmitter is shipped from the factory to indicate volumetric flow To display velocity in FPM enter...

Page 15: ...ALRM ON The Low Alarm is activated when the average airflow falls to a defined level below the SETPNT value The defined level is equal to the SETPNT value minus the calculated value of TOL value SETPN...

Page 16: ...and temperature navigate to the OUTPUT TEST submenu in the TOOLS menu OUT1 and OUT2 tests are independently accessed and the output will maintain the selected until the ESC button is pressed and norm...

Page 17: ...ing information for individual sensor data 5 8 3 Sensor Addressing and Probe Positioning Sensors are automatically addressed after power is applied to the transmitter as follows The probe connected to...

Page 18: ...rement to Standard units SFPM SCFM AIRFLOW ACT Custom LCD Flow Text Blinking prompt at position of the selected character Character is selected using the up and down arrows and then ENTER to accept an...

Page 19: ...t SW2 PCB switch setting VDC or mA for AO2 Pressing enter displays SET SW2 ON PCB prompt to confirm SW2 PCB setting AO2 output is assigned as an airflow alarm output Refer to ALARM settings part 4 AO2...

Page 20: ...eft Enter gateway IP address use up down arrow buttons to select value and press ENT to move to right and ESC to move to left Set BACnet IP or Ethernet protocol SET IP SET NETADDRESS NETWORK IP 10 0 0...

Page 21: ...responding alarm BACnet object or Modbus register Alarm will only clear when alarm is not active O O HI ALRM OFF SET HI ALRM HI ALRM OFF Enable disable HI alarm LO ALRM OFF Enable disable LO alarm LO...

Page 22: ...2 TEST SET OUT2 TEST OUT2 TEST 0 OUTPUT TEST FIELD ADJUST RUN FA WIZARD SET FAW INT FAW INT 300 ADJUSTMENTS OFF 0 SET OFF OUT1 TEST SET OUT1 TEST OUT1 TEST 0 FLOW ADJ ON GAIN 1 000 SET GAIN GAIN 1 000...

Page 23: ...YES Displays active trouble codes and their descriptions Contact EBTRON customer service for recommended service information Set DSBL TRBL YES to ignore currently displayed TRBL alarm To disable all...

Page 24: ...T SIGNAL 1 2 COM ANALOG OUTPUT OUT 2 TEMP OR ALARM OUTPUT SIGNAL ANALOG BAS CONTROL INTERFACE OUT 2 can be set for analog Temperature Alarm or Trouble output Alarm output can be set as active high or...

Reviews: