Operating and Maintenance Instructions
210-OMI14229-Iss8.1
CN1116 Full OMI
Page 45 of 47
© ebm-papst UK Ltd 2021
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
H17
–
Adv. Settings
–
0-10V Control Cap H18
–
Adv. Settings
–
0-10V Input Cap
H19
–
Advanced Settings
–
Alarm Output
H20
–
Advanced Settings
–
BMS Settings
This submenu is only available when
OP Mode = Monitor
This submenu is only available when
OP Mode = Monitor & Control and the
control mode includes the “0
-
10V Input” option
The “Vol/Press Alarm” option is only available when monitoring a sensor or when OP Mode = Constant Volume/Pressure
The “Sensor Fail Alarm” option is only available when using sensors with the “fan sensor input” configuration
“Fan Min ADC” is a fixed reference value that indicates the lowest pressure identifiable by the 0
-10V input of the fans and it applies
to all fans within the fan array