Drawing   : - TPC406 
Issue 

: - 3 

Date 

: - 08/08/14 

 

 

OPERATION 

 
 

The  following  procedures  should  be  followed  to  test  the  RM85  for  correct 
operation: 
 

 

1. 

After  unpacking,  examine  all  external  features  to  confirm  damage-
free shipment. Report all defects and damage at once.  Connect the 
power cable to a grounded 13 Amp electrical outlet. 

 
 

2. 

Check dehumidification process as follows: 

 

 

 

 

A. 

Place unit on a level surface. 

 

 

B. 

Start up unit by switching to “I”. 

 

 

C.   Check that the compressor is running.   

 

 

D. 

Leave the machine running for 15 minutes. 

 

 

E.   Observe the evaporator coils through the front grille, to confirm 

frost formation or weeping. 

 

   

 

i. 

If  the  air  temperature  is  below  25

°

C,  an  even  coating  of 

frost should cover the entire evaporator coil.   

   

 

ii. 

If the air temperature is above 25

°

C, frost and/or droplets 

of condensed water should cover the entire evaporator coil. 

 

   

F. 

When  the  unit  is  operated  in  ambient  of  less  than  15°C,  a 
defrost  cycle  should  occur  approximately  every  hour.  The 
exact  time  is  impossible  to  predict  as  the  unit  is  fitted  with  a 
temperature sensitive defrost control. 

 

If, after carrying out the above procedures, the unit does not appear to 

function properly, refer to the 

Trouble Shooting

 section, which follows, 

or contact the Factory Service Center. 

 
 
 
 
 
 
 
After using the RM85, turn it off for five minutes to allow the condensate on 
the coils to drain into the pump reservoir, then turn it back on and press the 
momentary purge switch for twenty to thirty seconds to evacuate the water 
from the pump reservoir. 

CAUTION: 

DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION 

CAUTION: 

ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT 

LEAST FIVE MINUTES BEFORE RESTARTING. 

Summary of Contents for RM85 10560RG-GB

Page 1: ...Page 1 of 8 Drawing TPC406 Issue 3 Date 08 08 14 RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradua...

Page 3: ...l GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the pr...

Page 4: ...i If the air temperature is above 25 C frost and or droplets of condensed water should cover the entire evaporator coil F When the unit is operated in ambient of less than 15 C a defrost cycle should...

Page 5: ...roplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains c...

Page 6: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 8: ...ch 3036779 1 17 Fan 3040278 1 18 Fan inlet ring 3040283 1 19 Wheel 3050124 2 20 Rubber foot 3101436 2 21 Condensate pump 3160151 1 22 Compressor 3944933 1 UK Head Office Ebac Industrial Products Ltd S...