REPAIRS 

 

 

1. 

Should  an  electrical  component  fail,  consult  the  Factory  Service 
Center to obtain the proper replacement part. 

 

 

 

2. 

If refrigerant gas is lost from the machine, it will be necessary to use 
a  refrigeration  technician  to  correct  the  fault.    Contact  the  Factory 
Service Center prior to initiating this action.  

 

 

 

Any  competent  refrigeration  technician  will  be  able  to  service  the 
equipment.  The following procedure must be used: 

 

 

a.  The source of the leak must be determined and corrected. 

 
 

 

b.  The  machine  should  be  thoroughly  evacuated  before 

recharging. 

 

 

 

 

c.  The  unit  must  be  recharged  with  refrigerant  measured 

accurately by weight. 

 
 

 

d.  For evacuation and recharging of the machine, use the crimped 

and brazed charging stub attached to the side of the refrigerant 
compressor. 

 

 

 

 

The  charging  stub  should  be  crimped  and  rebrazed  after 
servicing.  

N

EVER

 

allow permanent service valves to be fitted to 

any part of the circuit.  Service valves may leak causing further 
loss of refrigerant gas. 

 

 

 

3. 

The  refrigerant  compressor  fitted  to  the  dehumidifier  is  a  durable 
unit that should give many years of service.  Compressor failure can 
result from the machine losing its refrigerant gas.  The compressor 
can be replaced by a competent refrigeration technician.   

 
 

 

Failure  of  the  compressor  can  be  confirmed  by  the  following 
procedure: 

 

 

a.  Establish  that  power  is  present  at  the  compressor  terminals 

using a voltmeter. 

 

 

 

b.  With the power disconnected, check the continuity of the internal 

winding  by  using  meter  across  the  compressor  terminals.    An 
open circuit indicates that the compressor should be replaced. 

 

 

 

c.  Check that the compressor is not grounded by establishing that 

a  circuit  does  not  exist  between  the  compressor  terminals  and 
the shell of the compressor. 

 

Summary of Contents for RM85 10560RG-GB

Page 1: ...Page 1 of 8 Drawing TPC406 Issue 3 Date 08 08 14 RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradua...

Page 3: ...l GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the pr...

Page 4: ...i If the air temperature is above 25 C frost and or droplets of condensed water should cover the entire evaporator coil F When the unit is operated in ambient of less than 15 C a defrost cycle should...

Page 5: ...roplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains c...

Page 6: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 8: ...ch 3036779 1 17 Fan 3040278 1 18 Fan inlet ring 3040283 1 19 Wheel 3050124 2 20 Rubber foot 3101436 2 21 Condensate pump 3160151 1 22 Compressor 3944933 1 UK Head Office Ebac Industrial Products Ltd S...

Reviews: