ROUTINE MAINTENANCE 

 
 

 
 
 
 
 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 

 

 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing 
the  dirt  out  from  behind  the  fins  with  compressed  air.  Hold  the 
nozzle of the air hose away from the coil to avoid damaging the fins. 
Alternatively, vacuum clean the coils. 

 
 
 
 
 

 

2. 

Check that the fan rotates freely.  

The fan motor is sealed for life 

and therefore does not need oiling.

 

 

 

3. 

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and 
observe  the  evaporator  coil.  It  should  be  evenly  coated  with  frost 
across  its  surface.    At  temperatures  above  25

°

C,  the  coil  may  be 

covered  with  droplets  of  water  rather  than  frost.    Partial  frosting 
accompanied by frosting of the thin capillary tubes, indicates loss of 
refrigerant gas or low charge.  

 

 

4. 

Check all  wiring connections, including mains cable for damage or 
loose connections. 

 

 

5. 

In  order  to  check  the  defrost  operation,  the  unit  needs  to  be 
operated in an ambient temperature of less than 15°C for at least 1 
hour.  When  operated  In  this  condition  the  unit  should  defrost  at 
least  once  every  hour.  The  defrost  mode  can  be  monitored  by 
observing  the  ice melting  on  the  coil face, prior  to  defrost  the face 
will show a white coating of frost, which should clear during defrost 

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 

PREVENT PERMANENT DAMAGE

.

   

 

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE

 

MAINTNENANCE

 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

Summary of Contents for RM85 10560RG-GB

Page 1: ...Page 1 of 8 Drawing TPC406 Issue 3 Date 08 08 14 RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradua...

Page 3: ...l GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the pr...

Page 4: ...i If the air temperature is above 25 C frost and or droplets of condensed water should cover the entire evaporator coil F When the unit is operated in ambient of less than 15 C a defrost cycle should...

Page 5: ...roplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains c...

Page 6: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 8: ...ch 3036779 1 17 Fan 3040278 1 18 Fan inlet ring 3040283 1 19 Wheel 3050124 2 20 Rubber foot 3101436 2 21 Condensate pump 3160151 1 22 Compressor 3944933 1 UK Head Office Ebac Industrial Products Ltd S...

Reviews: