Tripping characteristics
41
10/13 MN03402007Z-DE/EN
Test of auxiliary contacts 95/96, 97/98
An additional Test button enables the operation of the auxil-
iary contact to be checked. The Test button has a dual func-
tion here:
• Pressing the Test button opens the NC contact 95-96.
The contact recloses after the button is released.
This function can be used for switching off the motor
manually.
• Pulling the Test button causes the overload relay to trip.
NC contact 95-96 opens and NO contact 97-98 closes.
After the Test button is released, the overload relay must
be reset in the same way as after a trip.