Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
For conduit box and anchor point locations and dimensions, see
.
Ensure the exposed conduit location is in the proper location relative to the conduit opening in the bottom of
the xStorage 400. If the conduit is installed in the incorrect location, the power cabling can be rerouted and
installed using a side entrance kit.
2.
If not already accomplished, using the forklift openings on the bottom of the cabinet, use a forklift to move
the xStorage 400 to the installation site. See
, and
for the cabinet center of
gravity measurements.
3.
Carefully align the xStorage 400’s conduit opening with the exposed conduit in the concrete pad, and
lower the xStorage 400 onto the concrete pad.
Figure 13. Conduit Box and Anchor Point Locations
Conduit Junction Box
Bottom View of the xStorage Cabinet
Floor Anchor Locations
(8x)
4.
Using the supplied anchor bolts and hardware, secure the xStorage 400 to the concrete pad.
See paragraph
for anchoring bolt locations and installation
specifications.
5.
Using the supplied hardware, install the forklift opening plates to the eight openings around the base of the
xStorage 400, see
for plate installation process.
Summary of Contents for xStorage 400
Page 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Page 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Page 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Page 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Page 96: ...P 16400103201 P 164001032 01...