20
Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
Table 3. External Power Cable Terminations
Terminal Function
Terminal
Function
Buss Landings
Tightening
Torque
Nm (lb-ft)
Bolt Size
AC Input and Output
L1
Phase A
4 – 2 bolt landing
76 (56)
M12
L2
Phase B
4 – 2 bolt landing
76 (56)
M12
L3
Phase C
4 – 2 bolt landing
76 (56)
M12
Ground
Ground
Ground
4 – 2 bolt landing
48 (36)
M10
Table 4. 480V Power Cable Conduit Requirements
Terminal
Number of Wires
Min. Conduit Trade Size
(inches)
Number of Conduits
AC Input / Output
4
2.5
3
Table 5. Recommended Feeder Circuit Breaker Ratings
% Breaker Rating
480V
100% Rated
600 A
80% Rated
700 A
33..22..44
IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the interface terminal blocks located inside the
xStorage 400.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required. All conduit components and installation methods must be weatherproof.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
•
Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
rated for 24V, 1A minimum. When Class 2 circuit wiring must be mixed with Class 1 wiring, use Class 1
wire and wiring methods.
•
Use twisted-pair wires for each input and return or common.
•
All interface wiring and conduit is to be supplied by the installer.
•
When installing external interface wiring to the xStorage 400 interface terminals, weatherproof conduit
must be installed between each device and the xStorage 400 enclosure.
•
Install the interface wiring in separate weatherproof conduit from the power wiring.
Summary of Contents for xStorage 400
Page 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Page 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Page 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Page 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Page 96: ...P 16400103201 P 164001032 01...