Xenon beacon Xb15
TM332 Issue A
October
2018 www.eaton.com
Xenon beacon XB15
English
Access to terminals
Unscrew the grub screw (2.0mm A/F hexagon key) in the
flange of the cover 3 full turns (Do not fully unscrew).
Unscrew and remove the cover and lens assembly using
the spanner supplied to gain access to the inside of the
unit. Unscrew the 2 off thumbscrews and carefully lift
the PCB assembly clear of the mounting pillars to gain
access to the terminals.
Once termination is complete, replace the PCB
assembly onto the mounting pillars and fully tighten
the thumbscrews, taking care not to overtighten them.
Replace the cover assembly, ensuring the cover is fully
screwed down. There should be a maximum gap of
0.2mm between the faces of the cover and enclosure
to ensure o-ring compression. Ensure the cover seal is
correctly seated in its groove during re-assembly.
Re-tighten the grub screw (2.0mm A/F hexagon key) in
the cover flange to secure the cover.
Wiring detail
* Relay initiate option is not available for EN54-23 version