The telephone initiate versions of the Beacon are not 

included in this safety manual.
Under No fault (Normal) Operating conditions the XB15 

Beacon will provide a spherical visual warning light when 

required by the system.
Under fault conditions the failure mode of the Beacon is a 

failure to provide a spherical visual warning light. For the 

failure rate associated with this failure mode please refer 

to the table below.

Assessment of functional safety – XB15 DC

This Beacon is intended for use in a safety system 

conforming to the requirements of IEC61508.  Sira Test 

& certification Ltd has conducted a Failure Modes  Effect  

and  Diagnostic  Analysis (FMEDA) of the DC version of  

XB15 Xenon Beacon against  the requirements of  IEC 

61508-2 using a Proof Test Interval of 730hrs.
The results are shown below and are based on Route 1H. 

The Beacon is classed as a Type B device.

Safety function:

‘To provide a spherical cycled visual warning light when energized’.

Xb15 Dc beacon

Summary of Clauses

2/7.4.2 and 2/7.4.4

XB15 Xenon Beacon

Single Mode (1oo1)

XB15 Xenon Beacon

Redundant Mode (1oo2)

Verdict

Architectural constraints 

Safe Failure Fraction (SFF)

HFT=0

HFT=1

Type B

62%

62%

SIL 1

Random hardware 

failures: [h

-1

 ]

λ

DD

λ

DU

0.00E+00

5.85E-06

0.00E+00

5.85E-07

Random hardware 

failures: [h

-1

 ]

λ

SD

 

λ

SU

0.00E+00

9.53E-06

0.00E+00

9.53E-07

Diagnostic coverage (DC)

0.00%

0.00%

PFD @ PTI = 730Hrs, MTTR = 8 Hrs

2.18E-03

2.18E-04

SIL 2 (1oo1)

Average freq. of dangerous failure (high 

demand-PFH)[h

-1

]

5.85E-06

5.85E-07

SIL 1 (1oo1)

Hardware safety integrity compliance

[

Route 1

H

Systematic safety integrity compliance

See report R56A24816B

Systematic Capability

(SC1, SC2, SC3, SC4)

SC2

 (R56A24816B)

Hardware safety integrity achieved

Limited to: SIL 1 (1oo1) & SIL 2 (1oo2) due to SFF value.

Assessment of functional safety – XB15 AC

This Beacon is intended for use in a safety system 

conforming to the requirements of IEC61508. UL has 

conducted a Failure Modes Effect and Diagnostic 

Analysis (FMEDA) of the XB15 Xenon Beacon against the 

requirements of IEC 61508-2 using a Proof Test Interval of 

8760hrs.
The results are shown below and are based on Route 1

H

The Beacon is classed as a Type B device.

Xenon beacon Xb15

   

TM332 Issue A

   

October

 2018   www.eaton.com

Summary of Contents for XB15

Page 1: ...Technical manual Xenon beacon XB15...

Page 2: ...LAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT...

Page 3: ...ing replacing xenon tube 4 6 0 SPECIAL CONDITIONS FOR SAFE USE 4 7 0 CERTIFICATION APPROVALS 4 IECEx units 4 ATEX units 4 EN54 23 2010 visual alarm device beacon XB15 24Vdc units only 4 These units al...

Page 4: ...iv Xenon beacon Xb15 TM332 Issue A October 2018 www eaton com...

Page 5: ...hould be in accordance with specification applying to the required application MEDC recommends that all cables and cores should be correctly identified Please refer to the wiring diagram in this manua...

Page 6: ...ting pillars to gain access to the terminals Once termination is complete replace the PCB assembly onto the mounting pillars and fully tighten the thumbscrews taking care not to overtighten them Repla...

Page 7: ...little or no maintenance GRP will resist attack by most acids alkalis and chemicals and is as resistant to concentrated acids and alkalis as most metal products However if abnormal or unusual environm...

Page 8: ...ting TD Tamb 15J T4 T135 C 55 C to 70 C T5 T100 C 55 C to 40 C 10J T4 T135 C 55 C to 70 C T5 T100 C 55 C to 55 C T6 T85 C 55 C to 40 C 5J T5 T100 C 55 C to 70 C T6 T85 C 55 C to 55 C The IECEx certifi...

Page 9: ...The maximum height of the device on the wall in metres with a minimum value of 2 4 m y The width in metres of the square volume covered to a minimum level of 0 4 lux when the device is mounted at a he...

Page 10: ...7 4 2 and 2 7 4 4 XB15 Xenon Beacon Single Mode 1oo1 XB15 Xenon Beacon Redundant Mode 1oo2 Verdict Architectural constraints Safe Failure Fraction SFF HFT 0 HFT 1 Type B 62 62 SIL 1 Random hardware f...

Page 11: ...h 1 DD DU 6 45E 09 3 48E 07 6 45E 10 3 48E 08 Random hardware failures h 1 SD SU 0 00E 00 8 84E 07 0 00E 00 8 84E 08 Diagnostic coverage DC 0 00 0 00 PFD PTI 8760Hrs MTTR 8 Hrs 1 53E 03 1 53E 04 SIL 2...

Page 12: ...rongly recommended to test the product at least once a year 3 Selection of this equipment for use in safety functions and the installation configuration overall validation maintenance and repair shall...

Page 13: ...ICA O APROVA ES 13 Unidades IECEx 13 Unidades ATEX 13 EN54 23 2010 dispositivo de alarme visual sinalizador luminoso de xen nio XB15 apenas para unidades de 24Vcc 13 Essas unidades tamb m disp em das...

Page 14: ...conformidade com as especifica es referentes aplica o em quest o A MEDC recomenda que todos os cabos e condutores sejam identificados corretamente Consulte o esquema el trico reproduzido neste manual...

Page 15: ...coloque o conjunto da PCI em seus pilares de montagem e aperte firmemente os parafusos tendo o cuidado de n o aplicar aperto excessivo Substitua o conjunto da tampa assegurando se de que esta tenha si...

Page 16: ...GRP resiste ao ataque da maioria dos cidos bases e produtos qu micos em geral sendo resistente a cidos e bases concentrados como a maior parte dos produtos met licos Todavia recomenda se uma inspe o v...

Page 17: ...T100 C 55 C a 40 C 10 J T4 T135 C 55 C a 70 C T5 T100 C 55 C a 55 C T6 T85 C 55 C a 40 C 5 J T5 T100 C 55 C a 70 C T6 T85 C 55 C a 55 C O certificado IECEx e a etiqueta do produto cont m a marca o do...

Page 18: ...montado em paredes x A altura m xima do dispositivo na parede em metros com um valor m nimo de 2 4 m y A largura em metros do volume quadrado coberto a um n vel m nimo de 0 4 lux quando o dispositivo...

Page 19: ...C61508 2 usando um intervalo de teste de prova de 730 horas Os resultados s o mostrados abaixo e s o baseados na Rota 1H O sinalizador luminoso classificado como um dispositivo do Tipo B Fun o de segu...

Page 20: ...2 e 2 7 4 4 Sinalizador luminoso de xen nio XB15 Modo simples 1oo1 Sinalizador luminoso de xen nio XB15 Modo redundante 1oo2 Veredicto Limita es arquitet nicas Fra o de Falha de Seguran a SFF HFT 0 H...

Page 21: ...utras aplica es recomenda se fortemente testar o produto pelo menos uma vez ao ano 3 A sele o deste equipamento para uso em fun es de seguran a e a instala o configura o valida o geral manuten o e rep...

Page 22: ...ion contained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a...

Reviews: