3
Technical Data
TD450157EN
Effective August 2022
Eluxa horns, horn strobes, & strobes
EATON
www.eaton.com
Table 4. Specification & Ordering Information
Model
Mounting
Strobe Candela
Red
White
Lettering
Sync w/ DSM or
Wheelock Power Supplies
Horn strobes
ELHSR
ELHSW
ELHSR-A
ELHSR-N
ELHSW-A
ELHSW-AL
ELHSW-N
ELHSW-EV
ELHSRC
ELHSWC
ELHSWC-N
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Ceiling
Ceiling
Ceiling
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/150/177
15/30/75/110/150/177
15/30/75/110/150/177
X
X
X
X
X
X
X
X
X
X
X
FIRE
FIRE
AGENT
No Lettering
AGENT
ALERT
No Lettering
EVACUATE
FIRE
FIRE
No lettering
X
X
X
X
X
X
X
X
X
X
X
Strobes
ELSTR
ELSTW
ELSTR-A
ELSTR-AL
ELSTW-A
ELSTW-AL
ELSTW-N
ELSTR-N
ELSTW-EV
ELSTRC
ELSTWC
ELSTRC-AL
ELSTWC-AL
ELSTWC-EV
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Ceiling
Ceiling
Ceiling
Ceiling
Ceiling
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/135/185
15/30/75/110/150/177
15/30/75/110/150/177
15/30/75/110/150/177
15/30/75/110/150/177
15/30/75/110/150/177
X
X
X
X
X
X
X
X
X
X
X
X
X
X
FIRE
FIRE
AGENT
ALERT
AGENT
ALERT
No Lettering
No Lettering
EVACUATE
FIRE
FIRE
ALERT
ALERT
EVACUATE
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Horns
ELHNR
ELHNW
ELHNRC
ELHNWC
Wall
Wall
Ceiling
Ceiling
X
X
X
X
No Lettering
No Lettering
No Lettering
No Lettering
X
X
X
X
Accessories
ELSBB-R
ELSBB-W
ESB-KIT-R
ESB-KIT-W
LSPKBB-CR
LSPKBB-CW
LED Backbox, wall
LED Backbox, wall
Trim Plate, wall
Trim Plate, wall
Backbox, ceiling
Backbox, ceiling
X
X
X
X
X
X
a
RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For
strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for
24v units). For unfiltered FWR ratings, see installation instructions.
b
Regulated Voltage Range - VDC
Table 2. Strobe ratings
Eluxa Horn Strobes
UL/ULC Max Current
a
at Anechoic
High continuous
24VDC
Model
Regulated Voltage
Range VDC
15
30
75
110
135
150
177
185
ELHS
ELHSC
16.0-33.0
16.0-33.0
0.037
0.037
0.046
0.046
0.077
0.077
0.109
0.109
0.146
0.146
0.208
0.208
Table 3. Code 3 horn strobe ratings
UL/ULC Max Current
a
24VDC
Model
Regulated Voltage
Range VDC
15
30
75
110
135
150
177
185
ELST
ELSTC
16.0-33.0
16.0-33.0
0.022
0.022
0.030
0.030
0.060
0.060
0.086
0.086
0.125
0.125
0.185
0.185
Eluxa Horn Strobes
UL/ULC Max Current
a
at Anechoic
Low continuous
24VDC
Model
Regulated Voltage
Range VDC
15
30
75
110
135
150
177
185
ELHS
ELHSC
16.0-33.0
16.0-33.0
0.030
0.030
0.039
0.039
0.070
0.070
0.102
0.102
0.139
0.139
0.201
0.201
ote:
N
Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper
Wheelock Inc., dba Eaton standard terms and conditions.