background image

11

Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

Testing

All underground distribution switchgear is carefully 

tested and adjusted at the factory to operate according 

to published data. Well-equipped test facilities, a detailed 

testing procedure and thoroughly trained personnel assure 

accurately calibrated equipment. Each unit leaves the 

factory ready for installation.
Pre-installation testing is not necessary. However, should 

verification of switchgear prior to installation be required, 

the vacuum interrupters can be tested using the following 

procedures.

High-potential withstand testing of vacuum 

interrupters

High-potential withstand tests can be performed to 

check the vacuum integrity of the interrupters used in VFI 

switchgear.

Safety Requirements

 WARNING

Hazardous voltage . The switchgear (apparatus and 

control) and high-voltage transformer must be in a test 

cage or similar protected area to prevent accidental 

contact with the high-voltage parts . Solidly ground all 

equipment . Failure to comply can result in death, severe 

personal injury, and equipment damage . 

T221 .5

 CAUTION

Radiation . At voltages up to the specified test voltages, 

the radiation emitted by the vacuum interrupter is 

negligible . However, above these voltages, radiation 

injurious to personnel can be emitted . See Service 

Information MN280062EN, Vacuum Interrupter 

Withstand Test Voltage Ratings Information for further 

information . 

G109 .2

To prevent accidental contact with high-voltage parts, the 

switchgear and high-voltage transformer must be placed 

in a suitable test cage and all proper grounding procedures 

must be observed.
With the vacuum interrupters open (manual operating 

handle(s) in the Open position), perform an AC high-potential 

test for one minute (or 15 minutes for DC) across each open 

vacuum interrupter assembly at the voltages shown in  

Table 5

. The interrupter should withstand the test voltage 

and should not load down the source.

Table 5 .  High-Potential Withstand Test Voltages

VFI Voltage Rating (kV)

High-Potential* Test Voltages 

15

25.5 kV AC RMS or 39.75 kV DC

25

30 kV AC RMS or 58.5 kV DC

35

37.50 kV AC RMS or 77.25 kV DC

*  75% of the production AC withstand test voltage, per IEEE Std 

C37.60

TM

-2003 standard.

Trip and control testing

Eaton’s Cooper Power series VFI Tester device (

Figure 5

) is 

used for testing VFI underground distribution units equipped 

with Tri-phase or TPG controls. It is self-contained and 

provides quick verification of the correct operation of VFI trip 

mechanisms, supervisory controls, and accessory SCADA 

boards.
Refer to 

Service Information MN285001EN, VFI Tester 

Operating Instructions

 for complete information regarding 

operation of the VFI tester and in-depth VFI underground 

distribution switchgear testing procedures.
For VFI switchgear provided with Edison Idea relays, please 

refer to the following service manuals for trip and control 

testing:
For iTAP-265 relay:

 

CA165005EN: iTAP-265 Dual Overcurrent Relay

For iTAP-260 relay:

 

Service Information S165-260-1,Use and Operations 

Manual for the iTAP-260 Underground Distribution VFI 

Switchgear Controller

For iDP-210 relay:

 

CA165002EN: iDP-210 Feeder Protection Relay

Figure 5 .  VFI Tester Unit - Catalog Number KVFI TESTER

Summary of Contents for VFI

Page 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Page 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Page 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Page 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Page 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Page 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Page 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Page 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Page 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Page 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Page 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Page 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Page 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Page 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Page 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...

Reviews: