Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

WARNING

Do not operate this equipment if energized parts are not 

immersed in dielectric fluid . Operation when parts are 

not properly immersed in dielectric fluid may result in 

internal flashovers that will damage the equipment and 

can cause death or severe personal injury . 

G104 .4

Application

This switchgear must only be applied within its specified 

ratings. At no time should the continuous total load exceed 

the ratings shown on the nameplate.
This switchgear must always be filled to the correct level 

with mineral oil, Envirotemp™ E200 or Envirotemp™ FR3™ 

fluid.

Vacuum fault interrupters

The vacuum fault interrupter push/pull operating handles 

(shown in 

Figure 3

 and 

Figure 4

) are located on the 

switchgear front plates. A hotstick must be used to operate 

the handles of the vacuum fault interrupters.

 WARNING

Hazardous Voltage . Always use a shotgun stick when 

working with this equipment . Failure to do so could 

result in contact with high voltage, which will cause 

death or severe personal injury . 

G108 .0

Opening interrupter

The vacuum fault interrupter is opened by pulling the 

operating handle down to the open position. The handle 

may be padlocked in the open position to prevent accidental 

closure.

Resetting the vacuum fault interrupter

After the vacuum fault interrupter mechanism has tripped, 

as the result of a fault condition, the mechanism must be 

reset before it can be closed. To reset the mechanism, 

firmly pull the operating handle down toward the ground 

until the latch resets. After the latch has been successfully 

reset, the vacuum fault interrupter mechanism can be 

closed normally.

Closing the interrupter

The vacuum fault interrupter is closed by briskly pushing the 

handle up, into the closed position.

otee:

N

In many configurations, a Type RVAC switch is 

integrated within the VFI switchgear. Refer to the 

Operation section of 

MN285005EN Type RVAC Fluid-

Insulated Vacuum Switchgear; Installation, Operation, 

and Maintenance Instructions

 for operation 

information for the RVAC switch.

Loadbreak switch

In most configurations, a Type RVAC loadbreak switch is 

integrated within the VFI switchgear. The switch’s push-to-

close/ pull-to-open handle is operated with a clampstick. 

The switch can be padlocked in either position, and a key 

interlock is available for added security.

Maintenance information

 WARNING

This equipment relies on dielectric fluid to provide 

electrical insulation between components . The dielectric 

strength and moisture content of the fluid must be 

checked on a regular basis, as part of the routine 

maintenance inspection, to ensure that it is at or 

above minimum dielectric requirements and below the 

maximum moisture content . Use of this equipment 

with dielectric fluid that does not meet requirements 

can result in internal flashovers that will damage the 

equipment and can result in death or serious injury .  

G107 .3

 CAUTION

This equipment requires routine inspection and 

maintenance to ensure proper operation . If it is not 

maintained it can fail to operate properly . Improper 

operation can cause equipment damage and possible 

personal injury . 

G105 .1

The Type VFI switchgear is a deadfront design. All live parts 

are contained within the sealed tank enclosure. A routine 

maintenance inspection program is required to ensure 

proper operation. 
It is necessary to establish and maintain a regular schedule 

for sampling and testing the insulating fluid to ensure proper 

dielectric strength, moisture content and fluid levels in the 

switchgear.

Maintenance inspection procedure

The Type VFI switchgear must be de-energized, grounded, 

and removed from service before conducting any 

maintenance, fluid processing or fluid-filling procedures.

 WARNING

Hazardous voltage . This equipment must be 

de-energized and grounded prior to conducting any 

maintenance, dielectric fluid processing or dielectric 

fluid filling procedures . Failure to comply can result in 

death or severe personal injury . 

T239 .2

1. 

De-energize and ground switchgear .

2.

  Reduce internal tank pressure to 0 PSIG . 

The 

switchgear is equipped with a pressure relief valve 

that opens at 5 PSIG and closes at 3 PSIG. To relieve 

internal tank pressure, pull the ring on the pressure 

relief valve.

Summary of Contents for VFI

Page 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Page 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Page 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Page 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Page 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Page 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Page 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Page 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Page 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Page 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Page 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Page 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Page 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Page 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Page 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...

Reviews: