background image

10

Type VFI, Fluid-insulated Switchgear 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

   MN285006EN   March 2018

Dissolved gas analysis

Dissolved gas analysis is a useful technique for diagnosing 

abnormal conditions and assessing the “normal” condition 

of insulating fluid in fluid-filled equipment. The method 

employed is ASTM D3612, which is used in conjunction 

with IEEE Std C57.104™-2008 

I

EEE Guide for the Detection 

and Determination of Generated Gases in Oil Immersed 

Transformers and their Relations to the Serviceability of the 

Equipment. 

Table 4

 provides recommendations on dissolved 

gas levels in fluid insulated switchgear.

Table 2 .  Test limits for service-aged fluid

Fluid Test

Method

Requirement

Dielectric Strength
Acid*
Dissipation*
Interfacial*
Water Content

D877
D974
D924
D971
D1533

26 kV minimum
0.20 mg KOH/g maximum
1.0% maximum
24 mN/m minimum
See 

Table 3

*Requirements shown are for mineral oil only. Service-aged limits for ester 

fluids have not been established at the time of this publishing.

Table 3 .  Service recommendations for insulating fluid moisture contents

Fluid Type

Water Content (ppm)

Service Recommendation

Mineral Oil

< 25

Continue with Eaton recommended maintenance schedule (inspection and sampling every 2 years).

25 – 35

Obtain another fluid sample for moisture analysis in 6 months to determine if moisture levels are rising. Refer 

to the 

Fluid sampling guidelines 

section in this manual. If moisture levels increase, determine leak 

point and repair. Process or replace the fluid if water conent has exceeded 35 ppm. 

> 35

De-energize the equipment immediately. Take another sample and verify results. If verified, process or replace 

the fluid before returning to service.

FR3  

< 400

Continue with Eaton recommended maintenance schedule (inspection and sampling every 2 years). 

400 – 600

Obtain another fluid sample for moisture analysis in 6 months to determine if moisture levels are rising. Refer 

to the 

Fluid sampling guidelines

 section in this manual. If moisture levels increase, determine leak 

point and repair. Process or replace the fluid if water conent has exceeded 600 ppm. 

> 600

De-energize the equipment immediately. Take another sample and verify results. If verified, process or replace 

the fluid before returning to service.

E200

< 800

Continue with Eaton recommended maintenance schedule (inspection and sampling every 2 years). 

800 – 1200

Obtain another fluid sample for moisture analysis in 6 months to determine if moisture levels are rising. Refer 

to the 

Fluid sampling guidelines

 

section in this manual. If moisture levels increase, determine leak 

point and repair. Process or replace the fluid if water conent has exceeded 1200 ppm. 

> 1200

De-energize the equipment immediately. Take another sample and verify results. If verified, process or replace 

the fluid before returning to service.

Table 4 .  Dissolved gas in insulating fluid maintenance 

chart

Acetylene Level 

C2H2

Total Combustible 

Gas

Required Action 

Less than 35 ppm

Less than 500 ppm

Normal Level - Resample 

per routine maintenance 

schedule

35-50 ppm

500-1000 ppm

Caution Level - Resample 

at 3-6 months to espablish 

trend; maintain fluid if 

gas levels increase to 

hazardous level.

More than 50 ppm

More than 1000 

ppm

Hazardous Level - Remove 

unit from service and 

maintain the fluid.

Replacement parts

Only factory-authorized replacement parts are to be used 

for Eaton’s Cooper Power series Distribution Switchgear 

products. Replacement parts are available through the 

factory Service Department. To order replacement parts, 

refer to the nameplate and provide the product type, serial 

number, catalog number, voltage rating, and a description 

of the part. Contact your Eaton representative for additional 

information and ordering procedures. The following 

documents are also available for common field repairs and 

procedures:

 

MN285009EN – Cover gasket replacement, cover 

instalation, leak check procedures and fluid sampling 

porcedures.

 

MN285007EN – Visible break window replacement 

procedure.

Summary of Contents for VFI

Page 1: ...Type VFI Fluid insulated Switchgear Installation Operation and Maintenance Instructions COOPER POWER SERIES Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015...

Page 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Page 3: ...binet construction 3 Standard features 3 Interrupter duty cycle 3 Switch test sequence 3 Finish 3 Nameplate 3 Operating handles 3 Weight 4 Special certifications 4 INSTALLATION PROCEDURE 4 OPERATION 5...

Page 4: ...hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 5: ...e pallet Improper handling can cause damage to the switchgear If the switchgear is to be stored for any appreciable time before installation provide a clean dry storage area Be careful during handling...

Page 6: ...llation Operation and Maintenance Instructions for operation information for the RVAC switch Vacuum fault interrupters Load and fault interruption takes place within sealed vacuum interrupters Figure...

Page 7: ...37 74TM 2003 standard Padlocking provisions Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening The cabinet must be locked at all times to prevent accident...

Page 8: ...tances where a UL listing is required Figure 3 VFI switchgear operating handle three phase ganged operation Figure 4 VFI switchgear operating handles single phase operation Installation procedure WARN...

Page 9: ...T223 2 5 Ground switchgear Switchgear must be adequately grounded Install a permanent low resistance ground connection to the switchgear tank Grounding provisions are provided near the bottom of the t...

Page 10: ...aintenance Instructions for operation information for the RVAC switch Loadbreak switch In most configurations a Type RVAC loadbreak switch is integrated within the VFI switchgear The switch s push to...

Page 11: ...ith sampler at the bottom of the tank If moisture is found in the tank refill with clean dry insulating fluid WARNING Hazardous voltage This equipment must be de energized and grounded prior to conduc...

Page 12: ...ry T239 2 Use the following fluid sampling guidelines to prevent contamination and to safely extract fluid samples 1 De energize and ground the switchgear prior to sampling fluid 2 Where local governi...

Page 13: ...from altering the moisture content of the sample Leave about one inch of air space in the container to account for thermal expansion 15 Retighten sampling valve to finger tight plus a 1 4 turn Reinsta...

Page 14: ...e if moisture levels are rising Refer to the Fluid sampling guidelines section in this manual If moisture levels increase determine leak point and repair Process or replace the fluid if water conent h...

Page 15: ...arts the switchgear and high voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed With the vacuum interrupters open manual operating handle s...

Page 16: ...es Eaton com cooperpowerseries 2018 Eaton All Rights Reserved Printed in USA Publication No MN285006EN March 2018 KA20480375 Rev 09 Eaton is a registered trademark All trademarks are property of their...

Reviews: