4. Press several times until appears on the
display.
5. Press for at least 5 seconds. The display will begin to
flash and the auto-tuning procedure will begin.
2. Set the correct values for the setup menu of the unit.
But don't use a zero value for PB and TI, otherwise, the
auto-tuning program will be disabled. The LOCK parameter
should be set at NONE.
3. Set the set point to a normal operating value or a lower value if
overshooting beyond the normal process value is likely to
cause damage.
The ramping function, if used, will be disabled once auto-tuning
mode is entered.
The auto-tuning mode is disabled as soon as either failure mode
or manual control mode occurs.