2
EATON
IB505051EN Installation instructions
Installation Instructions for LPX Combination Exit/Emergency Lights and Exits with Self
Diagnostics
CEILING OR END MOUNT INSTALLATION
1 Extend unswitched 24 hour AC supply of rated voltage to
junction box (by others). Leave at least 18 inches of slack.
Circuit should not be energized at this time.
2 Remove the stencil face and lens assembly by applying a
screwdriver to the snaps located at the top and bottom of
the stencil face.
3 If mounting the canopy to the top, remove the canopy hole
cover plate on the top. If locating the canopy on the side,
first remove the left side head by disconnecting the LED
lamp wires from the PCB (see Schematic) and gently pulling
on the head mount (see Figure 2). The head may now be
mounted in one of the 3 locations on the top (see Figure 2).
The center top mounting point can be accessed by removing
the cover. The left and right top mounting points can be
accessed by removing the small knock outs. The left side
head can also be moved to the top, to make the fixture
symmetric. Cover the unused holes with the canopy hole
cover plates.
4 If double face sign is required, convert the single face sign
supplied. Replace back plate with extra stencil and color
sheet supplied with the sign.
5 Place the canopy nose through the mounting hole until the
side of the frame touches the canopy. Lock the frame onto
the canopy by sliding the frame in a direction parallel to the
canopy length toward the narrow end of the mounting hole.
Slide the frame until both snaps engage the canopy nose
preventing any motion back out of the hole.
6 Mount mounting strap to junction box by choosing proper
slots and using screws supplied with junction box.
7 Feed the wires through the canopy.
Note:
Connections must be the enclosure rated area of the
frame (top left corner) or junction box (see Figure 1).
8 Connect power supply and ground in accordance with
local codes. Wire connections as follows: 277VAC/240VAC
line to Orange lead or 120V line to Black lead; Neutral or
240V (Common) to white lead. Ground to Green screw on
mounting strap. Cap unused line lead.
9 Connect the canopy to the mounting strap using the screws
provided.
10 Determine which color sign face is needed. If red is needed,
proceed to step 13.
ENCLOSURE RATED AREA.
WIRE CONNECTIONS
SHOULD BE MADE HERE
OR IN JUNCTION BOX.
DO NOT MAKE WIRE
CONNECTIONS IN
SIGN FACE
INTEGRATED WIRE HOOK
JUNCTION
BOX
KNOCK
OUTS
TO JUNCTION BOX
CANOPY
HOLE PLUG
REMOVE KOS
TO MOUNT
HEAD
MOUNTING
STRAP
TO
JUNCTION
BOX
Figure 1
Figure 2