background image

2

EATON

     IB505051EN     Installation instructions

Installation Instructions for LPX Combination Exit/Emergency Lights and Exits with Self 

Diagnostics

CEILING OR END MOUNT INSTALLATION 

1  Extend unswitched 24 hour AC supply of rated voltage to 

junction box (by others). Leave at least 18 inches of slack. 
Circuit should not be energized at this time.

2  Remove the stencil face and lens assembly by applying a 

screwdriver to the snaps located at the top and bottom of 
the stencil face.

3  If mounting the canopy to the top, remove the canopy hole 

cover plate on the top. If locating the canopy on the side, 
first remove the left side head by disconnecting the LED 
lamp wires from the PCB (see Schematic) and gently pulling 
on the head mount (see Figure 2).  The head may now be 
mounted in one of the 3 locations on the top (see Figure 2). 
The center top mounting point can be accessed by removing 
the cover.  The left and right top mounting points can be 
accessed by removing the small knock outs.  The  left side 
head can also be moved to the top, to make the fixture 
symmetric.  Cover the unused holes with the canopy hole 
cover plates.

4  If double face sign is required, convert the single face sign 

supplied. Replace back plate with extra stencil and color 
sheet supplied with the sign. 

5  Place the canopy nose through the mounting hole until the 

side of the frame touches the canopy. Lock the frame onto 
the canopy by sliding the frame in a direction parallel to the 
canopy length toward the narrow end of the mounting hole. 
Slide the frame until both snaps engage the canopy nose 
preventing any motion back out of the hole.

6  Mount mounting strap to junction box by choosing proper 

slots and using screws supplied with junction box.

7  Feed the wires through the canopy.   

Note:

 Connections must be the enclosure rated area of the 

frame (top left corner) or junction box (see Figure 1).

8  Connect power supply and ground in accordance with 

local codes. Wire connections as follows: 277VAC/240VAC 
line to Orange lead or 120V line to Black lead; Neutral or 
240V (Common) to white lead. Ground to Green screw on 
mounting strap. Cap unused line lead. 

9  Connect the canopy to the mounting strap using the screws 

provided.

10 Determine which color sign face is needed. If red is needed, 

proceed to step 13.

ENCLOSURE RATED AREA.  

WIRE CONNECTIONS 

SHOULD BE MADE HERE 

OR IN JUNCTION BOX.

DO NOT MAKE WIRE 

CONNECTIONS IN 

SIGN FACE

INTEGRATED WIRE HOOK

JUNCTION 

BOX 

KNOCK 

OUTS

TO JUNCTION BOX

CANOPY

HOLE PLUG

REMOVE KOS 

TO MOUNT 

HEAD

MOUNTING 

STRAP

TO 

JUNCTION 

BOX

Figure 1

Figure 2