     IB505051EN     Installation instructions

Installation Instructions for LPX Combination Exit/Emergency Lights and Exits with Self 

Diagnostics

11 If green is the desired color, remove the red lens from 

the stencil(s) and replace it with the green lens provided. 
(Installation is the reverse of removal).

12 On the LED circuit board, locate the red/green jumper (See 

Schematic).The jumper should be in the red position per the 
silk screen printing on the board. Pull gently upward on the 
jumper, then shift it one pin over to activate the green LEDS.

13 If the unit has remote capacity, LED remotes can be 

connected using the violet (+) and yellow (-) wires. (See 
Schematic).

14 Energize AC supply, LED display will come on.
15 Replace stencil, colored lens.
16 Remove EZ Key to connect battery.  Battery will not charge 

with EZ key in place. Allow 24 hours for charging with 120 or 
277V input, 48 hours with 240V input.

 

ACTIVATING OPTIONAL FLASHER

If the consumer desires the exit sign to flash on and off when 
in emergency mode, remove the jumper labeled FLASHER/J2 
from the circuit board while unit is de-powered. See Schematic. 

ACTIVATING TIME DELAY

The LPX Combo has an integrated time delay circuit that allows 
the heads to remain in emergency mode 15 minutes after 
power is restored. Remove the jumper on the circuit board 
labeled TDI/J3 to activate the time delay. 

MAINTENANCE

None required. Replace the batteries as needed according 
to ambient conditions. However, we recommend that the 
equipment be tested regularly in accordance with local codes.

NOTE:

 Servicing of any parts should be performed by qualified 

personnel. Only use replacement parts supplied by Eaton’s 
Lighting business.

CAUTION:

 This equipment is furnished with a sophisticated low 

voltage battery dropout circuit to protect the battery from over 
discharge after its useful output has been used. Allow 24 hours 
recharge time if connected to 120 or 277V, 48 hours with 240V, 
after installation or power failure for 90 minute testing. 

TROUBLE SHOOTING GUIDE 

If LED display or charge indicator LED does not illuminate, 
check the following:
•  Check AC supply – verify that unit has 24 hour AC supply.

If LEDs do not light in emergency mode but Charge indicator 
LED is on before test:
•  Unit is shorted or battery is not connected.
•  Battery discharged. Permit unit to charge for 24 hours (120 

or 277V) or 48 hours (240V) and then re-test.

If following the above trouble shooting hints does not solve 
your problem, contact your local Eaton Lighting representative 
for assistance.

WARRANTIES AND LIMITATION OF LIABILITY

Please refer to 

www.eaton.com/LightingWarrantyTerms

 for our 

terms and conditions.

WHITE LEAD - TO NEUTRAL OR 240V (COMMON)

ORANGE LEAD - TO 240 OR 277V

BLACK LEAD - TO 120V

ON BOARD

LED HEAD

ON BOARD

LED HEAD

BATTERY

2ND BATTERY

(HIGH POWER

MODELS ONLY)

REMOTE HEADS

(NOT INCLUDED)

POWER

SUPPLY PCB

REMOVE JUMPER TO

ACTIVATE TIME DELAY

SHIFT JUMPER TO

CHANGE LEDS FROM

RED TO GREEN

REMOVE

JUMPER TO

ACTIVATE

FLASHER

D4

F2

C1

F1

J1

C2

C3

+

MOV1

MOV2

Y

O

B

W N

120

277

R
B

041-1418 REV B

-

+

041-1420 REV A

ICSP

GREEN

RED

+

-

+

FLASHER

POWER

BATT

J1

FAI

+

TDI

BATT

-

RMT

+

+

+

+

C11

JP14

JP13

JP10

JP9

JP8

JP7

JP4

JP3

JP11

JP19

JP18

+

C1

CN7

LED6

LED5

LED8

LED7

LED9

LED10

LED4

LED3

LED2

LED1

J2

L1

CN4

C7

CN8

J3

JP2

JP17

JP15

CN6

CN5

CN3

JP6

JP12

C13

CN1

CN2

BW

JP1

Q14

JP5

Schematics

Reviews: