Instruction Leaflet

 IL01301074E

Effective July 2016

Series NRX PT module installation and  
operation instructions 
  

EATON 

www.eaton.com

Section 3. Operation

Switches are provided to disconnect each phase from the mains 
(Figure 9).  All three switches must be in the off (“O”) position before 
performing dielectric testing of a system where the PT module is 
connected.  When the test is complete, all switches must be in the on 
(“I”) position for the module to function as intended. 

• 

CAUTION

DIELECTRIC TESTING OF A SYSTEM CONTAINING A PT MODULE WITH THE 
PHASE CONNECTED WILL DAMAGE THE PT MODULE.  DISCONNECT ALL 
OF THE PHASES FROM THE MAINS (BY SELECTING “0”) BEFORE TESTING.  
AFTER TESTING, RETURN ALL PHASE SWITCHES TO THE “I” POSITION.

Figure 9. Line phase switches.

:

Line phase switches