Series NRX PT module installation and  

operation instructions 

  

EATON 

www.eaton.com

Instruction Leaflet

 IL01301074E

Effective July 2016

Figure 6. 

LA

LB

LC

PT

MODULE

BREAKER

A

0-690     L-L INPUT

B

C

To additional

breakers

Secondary

contacts

1

N

3

5

31 VB
30 VA

32 VC

TP2

14 VN

LN

Series NRX breakers with Digitrip 1150 trip units - 4-pole, 

4-wire.

Figure 7. 

LA

LB

LC

PT

MODULE

BREAKER

A

0-690     L-L INPUT

B

C

To additional

breakers

Secondary

contacts

1

N

3

5

30 VB
29 VA

31 VC

TP2

32 VN

LN

Series NRX breakers with PXR trip units - 4-pole, 4-wire.

The PT module secondary may connect up to 16 Series NRX breakers 
using 18 AWG wire for each phase in a daisy-chain configuration and 
may extend to the furthest breaker in the the chain, to a maximum of 
250 feet (Figure 8).

Figure 8. Daisy chain breaker connection of up to 16 breakers.

 250 ft (76.2 m) max.