2

Series NRX PT module installation and  

operation instructions 

  

EATON 

www.eaton.com

Instruction Leaflet

 IL01301074E

Effective July 2016

ote:

N

The content of this IL applies to both PXR and Digitrip equipped breakers.  

Appearance of product may vary.

Section 1. Description

The Potential Transformer (PT) module is a device used to supply a 
three phase voltage signal to series NRX NF-frame or RF-frame circuit 
breakers equipped with Digitrip 1150 or PXR programmable trip units. 

Specifications:

The output of the module is directly proportional to the input voltage 
according to the ratio given below (Table 1). 

Table 1.  Voltage ratios.

INPUT

OUTPUT (NORMAL)

208V L-L

1.95V L-N

240V L-L

2.25V L-N

415V L-L

3.89V L-N

440V L-L

4.13V L-N

480V L-L

4.50V L-N

600V L-L

5.63V L-N

690V L-L

6.47V L-N

 

• Maximum rated input voltage:  690 volts line to line

 

• Burden:  1 VA per phase

 

• Output voltage accuracy:  +/-2% of normal

Figure 1. 

5.716 (145.19)

4.406 (111.91)

FACE OF DIN RAIL

.755 (19.18)

2.896 (73.56)

.755 (19.18)

Dimensions of PT module.

• 

WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT 
WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL INJURY CAN 
RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY 
THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING.  ALWAYS FOLLOW 
SAFETY PROCEDURES.  EATON IS NOT LIABLE FOR THE MISAPPLICATION OR 
MISINSTALLATION OF ITS PRODUCTS. 

• 

WARNING

OBSERVE ALL RECOMMENDATIONS, NOTES, CAUTIONS, AND WARNINGS 
RELATING TO THE SAFETY OF PERSONNEL AND EQUIPMENT.  OBSERVE 
AND COMPLY WITH ALL GENERAL AND LOCAL HEALTH AND SAFETY LAWS, 
CODES, AND PROCEDURES.

ote:

N

The recommendations and information contained herein are based on 

experience and judgment, but should not be considered to be all-inclusive or to 
cover every application or circumstance that may arise. 