Installation
6
Eaton Remote Power Panel (RPP) User’s Guide 164202125—Rev 5
www.eaton.com/powerquality
The cabinet is shipped bolted to a wooden pallet and protected with outer protective packing material. Do not
remove protective packaging until the equipment is ready for installation. Do not loosen the cabinet from the
pallet until all forklift handling is complete.
To unpack the cabinet:
1.
Carefully inspect the outer packaging for evidence of damage during transit.
2.
Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. Insert the forklift or pallet jack's forks between the pallet supports on the bottom of the
unit.
Note:
Verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 16 on
page 43 for cabinet weight).
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
4.
Remove the protective outer packaging from the cabinet.
5.
Discard or recycle the packaging in a responsible manner, or store it for future use.
6.
Using a wrench, remove the two metal angle brackets at the base of the cabinet.
7.
Using a wrench, remove both front and back kick plates.
8.
Use the forklift or pallet jack to carefully lift the cabinet off the pallet and place it on the floor so that it is
resting on its casters.
CAUTION
l
The cabinet may roll when resting on its casters. Take proper care to secure the cabinet and ensure
the safety of personnel.
l
When the leveling feet are up and the cabinet is supported by casters only, do not stand on or in the
cabinet. The cabinet may tip, which may result in serious injury. Do not work on or in the cabinet until
the leveling feet are in place.
Checking the Accessory Kit
Verify that the following items are included inside the Remote Power Panel (RPP) cabinet:
Note:
To open a door, press the key insert to release the handle, turn the handle in either either direction
and swing the door open.
l
This user's guide.
l
Key to the lockable doors.
Note:
(Optional) After the RPP is installed, you can lock the cabinet with the key to prevent unauthorized
entry.
Locating the Cabinet
Follow these guidelines when locating the cabinet after unpacking:
l
Place the cabinet on a concrete or other non-combustible surface in a protected area that has adequate
airflow, access to a 120V service outlet, and is free of humidity, flammable gas, and corrosion.
l
Avoid placing the cabinet on its side.
WARNING
Take adequate precautions, as guided by a qualified structural engineer, when moving or placing this
equipment on a raised floor.