Appendix B: Digital Switch
PRC-E Series Instruction Manual
MN014003EN August 2015 www.eaton.com
Digital Switch field devices connections
Input wiring
Each Digital Switch has one analog input (AI) and one digital
input (DI). The digital input requires a dry contact closure
between the DI terminal and GND terminal. This input is
typically connected to a low voltage occupancy sensor or
any device with dry-contact output.
otee:
N
Digital input option is not available on 6-button
digital switches.
The analog input accepts 0–10 Vdc signal from external
devices.
The AI is typically connected to interior/exterior photo
sensors to monitor light levels
Output wiring
Each Digital Switch has one analog output (AO) to directly
control analog devices. The analog output provides
0–10 Vdc signal. This output is typically used to control
fluorescent and LED lighting equipped with 0–10 Vdc
dimming control circuitry. Up to 20 fluorescent ballasts or
10 LED drivers can be controlled.
External device power
Each digital switch includes a 12 Vdc/20 mA output (VOUT)
for connecting field devices such as, occupancy sensors and
photo sensors.
otee:
N
The power output of the switch has limited current
capabilities. Connecting devices that require the
higher current to this output will disable operation
of the switch.
Table 6 . Digital Switch I/O Configuration
Pushbutton
Configuration
Analog
Input
Analog
Output
Digital
Input
12 Vdc
Output
2-button
n
n
n
n
4-button
n
n
n
n
6-button
n
n
—
n
Figure 38 . Typical Digital Switch Field Devices Wiring
(+)
(-)
DSN from Previous
Digital Switch or
compatible PRC
controller
DSN
to next Digital Switch
*Note - for additional information on
the DSN see drawing
PRCE-DigitalSwitchNetwork
DSN Network
23 AWG Cat 6 Cable
Single Occupancy Sensor
w/ Dry-Contact Input
DI
AI
GND
AO
Vdc
Out
In
Photosensor
w/ 0 to 10 V Signal Level
To additional ballasts or LED drivers
Maximum 10 mA
GND
VDC (12V)
DI
DI
(Digital Input-
Not avilable on the
6-button switch)
AI
(Universal Input- analog
level or dry-contact)
GND
Ground- I/O common
AO
(Analog Output-
0–10 V 10 mA max)
VDC
(12 Vdc ext. device
supply 20 mA max)
AO
GND
AI
AO
GND
Vdc (12 V)
DI
AI
AO
Vdc (12 V)
DI
AI
LED Drivers and Fluorescent Ballasts
0 to 10 V Dimmable
GND
Vdc (12 V)
DI
AI
AO
Dry-Contact Override Switch
GND
DI
AI
AO
Multiple Occupancy Sensors
Require Switchpack
L N
Additional Occupancy
Sensors.
(See sensor manuals
for further information)
Vdc (12 V)
SP20-##
Blue
Blue
BLK
W
Dimming Circuit
(+ -)
OR
BK
R BL
GY
P
OR
BK
R BL
GY
P
OR
BK
R
GY
0