47
Web page programming
PRC-E Series Instruction Manual
MN014003EN August 2015 www.eaton.com
Logging into the PRC-E Web page
After entering the IP address of the PRC-E controller into
the address field of your browser, the secure login Web
page should open.
otee:
N
PRC Web Interface requires Adobe Flash Player.
Type the User name and password in the appropriate box
and click “OK”.
Default User name: admin
Default password: admin
A splash screen will open briefly.
The panelboards “Breakers” page will be the initial
Web page.
The Web pages are formatted in folder form. There are tabs
across the top of the Web page used to navigate to other
Web pages.
This guide is written in the order of an initial commissioning,
so the Web pages will not be covered in the order of the tabs
but all aspects of each will be covered. There are visible and
some context menu elements on each Web page.
Panelboard configuration
otee:
N
The Breaker Control Buses (BCBs) must be properly
addressed and all necessary SLAN wiring must be
terminated before continuing the following.
On initial commissioning or in the case of any newly added
PRCEP panelboard(s) to a system, the panelboard(s) must
be configured in the controller.
The panelboard configuration is made up of the panelboard
location; 1–8, the “Type” of panelboard; 42-circuit, 30-circuit,
18-circuit standard or column panelboard, the BCB’s
address; 1–8, the position within the panelboard; left side
or right side, and the name of the BCB.
By default, the panelboard configuration uses the BCB
addresses to set up a 42-circuit panelboard. The odd
addresses are assigned as left BCBs and the even
addresses are assigned as right BCBs.
To configure the panelboards:
Click the “System Configuration” tab.